
Controller Operation
15
)
Phase Protector/ Phase Failure Relay
13
)
Other Protection Device
Phase protector is installed on each condensing unit.
Function of phase protector
1. Phase reversal
2. Over or under voltage
3. Multiple type of fault auto recovery and lock function
Hardware Configuration
There is a 8 way DIP switch to program the 3 phase monitor according to the table below:
When there is fault occurred, red LED will blink according to the following error code:
Fault Error code
Over current protector (OLP), High pressure switch and low pressure switch are installed for
compressor protection.
When activated, compressor will be cut off, E04 will be displayed on the handset.
The error can be only be reset by cut off the main power supply and restart.
Check the system accordingly.
For unit with single speed motor , over current protector (OLP) is installed.
When activated , the power to the board will be cut off. To restart , reset the OLP.
Check on the airflow / external static of the unit.
DIP setting has been default set. User only recommended to set SW7 SW8 to local
Voltage supply. (Default setting 00 – 380V)
“0” – off “1” - on
Upon power up, the controller will blink the red LED quickly indicating at warm up stage.
This process may take a few seconds [0~20 sec depends on the voltage supply and
monitor settings]. Red LED will be off once the power supply is stable. Green LED and
relay will turn on 5 sec later.
Should the controller is unable to read the healthy 3 phase supply after 20 seconds, it
will lock the error and flash the red LED according to the alarm code.
It will check the power supply again 280 sec later. Upon confirmation of healthy 3 phase
supply, system will monitor the power supply constantly according to the DIP switch
settings. Should there be failure occurred, system will flash the red LED slowly until the
error delay time out and relay will be turn off. If the power supply is recovered before the
error delay time out, red LED will be off and system operate as normal.
System will lock the error if this failure happens ? 5 times within 2 hours. This fault can
be reset by manually turn off the power supply only.
SW1 SW2
SW3 SW4
SW5
SW6
SW7 SW8
Fault time delay
Voltage
tolerance
Reserved Voltage
measuring
3 phase input
00
-
5sec
01
-
10sec
10
-
15sec
11
-
20sec
00
-
5
%
01
-
10
%
10
-
15
%
11
-
20
%
0
-
Monitor
1
-
Bypassed
00
-
380V
01
-
400V
10
-
415V
11
-
440V
To select time
delay to confirm
fault
Check according
to SW7 SW8 setting
When set to ‘1’,
no under / over
voltage checking
will be done.
When set to ‘1’,
no under / over voltage
checking will be done
Over voltage
Blink 8 times, off 3 sec
Under voltage
Blink 7 times, off 3 sec
R phase failure
Blink 6 times, off 3 sec
S phase failure
Blink 5 times, off 3 sec
T phase failure
Blink 4 times, off 3 sec
Phase reversal
Blink 3 times, off 3 sec
11
Содержание KFDH100
Страница 16: ......