NEVER LEAVE HEATER UNATTENDED WHILE BURNING, 

CONNECTED TO A POWER SOURCE, OR WHILE 

CONNECTED TO A FUEL SOURCE

© 2017, Pinnacle Climate Technologies, Inc. 

Convection Heater User's Manual

Safety Information

The products described in this manual are 

propane direct-fired, forced air heaters. Propane 

forced air heaters are primarily intended for 

use for temporary heating of buildings under 

construction, alteration or repair. Direct-fired 

means that all of the combustion products of the 

heater enter the heated space. This appliance 

is rated at 98% combustion efficiency, but does 

produce small amounts of carbon monoxide.

Carbon monoxide is toxic. Humans can tolerate 

only small amounts of carbon monoxide and so 

precautions should be taken to provide proper 

ventilation. Failure to provide proper ventilation 

in accordance with the instructions in this manual 

can result in death.
People with breathing problems should consult a 

physician before using this heater. 
Early signs of carbon monoxide poisoning 

resemble the flu. Symptoms of improper 

ventilation / carbon monoxide poisoning are:

Headache • Dizziness • Nausea 

• 

Dry Mouth 

Sore Throat 

 Burning of Nose and Eyes

If you experience any of these symptoms:

 

GET FRESH AIR AT ONCE! 

Have your heater 

serviced and check for proper ventilation. Some 

people are more affected by carbon monoxide 

than others. These include: pregnant women, 

those with heart or lung problems, anemia or those 

under the influence of alcohol or at high altitudes. 

FOR OUTDOOR USE. INDOOR USE 

PERMITTED ONLY FOR: The temporary 

heating of adequately ventilated buildings or 

structures under construction, alteration or 

repair! Provide at least a three square foot  

(2,800 sq cm) opening of outside air for 

every 100,000 Btu / Hr heater rating. Refer to 

“Ventilation” on page 8 for further instructions. 

WHAT TO DO IF THE SMELL OF GAS IS PRESENT:

 

DO NOT attempt to light the heater.

 

Extinguish any open flame.

 

Shut off gas to heater.

 

If odor continues, contact your local gas 

supplier or fire department.

 

DO NOT touch or use any electric switch or 

any electric device that can cause a spark.

 

Immediately call your gas supplier from a 

neighbors phone. Follow the gas suppliers 

instructions.

 

If you can not reach your gas supplier, call 

the fire department. 

 

Service must be done by a qualified 

service agency.

NEVER store or use gasoline or other flammable 

vapors and liquids in the vicinity of this heater.
NEVER store

 

a propane (LP) cylinder not 

connected to this heater in the vicinity of this heater.

NEVER 

connect heater to an unregulated gas supply.

NEVER 

obstruct the flow of combustion and 

ventilation air. 
NEVER use duct work in front or rear of heater.
NEVER modify this heater or operate a heater that 

has been modified.
NEVER service, move or handle heater while still 

hot or operating
Keep all combustible materials away from this heater.

Minimum Clearance From Combustibles

Sides

Top

48 in.

96 in.

RISK OF INDOOR AIR 

POLLUTION!

WARNING

CARBON MONOXIDE POISONING 

MAY LEAD TO DEATH!

DANGER

RISK OF BURNS, FIRE AND 

EXPLOSION!

WARNING

PROPANE IS AN  

EXPLOSIVE GAS.

DANGER

CAUTION! HOT WHILE IN 

OPERATION. DO NOT TOUCH. 

KEEP CHILDREN, ANIMALS, CLOTHING AND 

COMBUSTIBLES AWAY FROM HEATER. 

WARNING

2

Содержание Remington REM-200V-LPC-O

Страница 1: ...THE MANUFACTURER DANGER FIRE BURN INHALATION AND EXPLOSION HAZARD KEEP SOLID COMBUSTIBLES SUCH AS BUILDING MATERIALS PAPER OR CARDBOARD A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THESE INS...

Страница 2: ...nd approved for use as a construction heater in accordance with Standard ANSI Z83 7 2011 CSA 2 14 2011 CHECK WITH YOUR LOCAL FIRE SAFETY AUTHORITY IF YOU HAVE ANY QUESTIONS ABOUT APPLICATIONS Other st...

Страница 3: ...NDOOR USE PERMITTED ONLY FOR The temporary heating of adequately ventilated buildings or structures under construction alteration or repair Provide at least a three square foot 2 800 sq cm opening of...

Страница 4: ...a from the heater and do not direct heater discharge towards the LP cylinder unless it is at least 20 feet from the heater Use only the regulator and hose assembly provided with this heater Inspect th...

Страница 5: ...e 2 Specifications Model REM 80V LPC O REM 200V LPC O BTU 60 000 70 000 80 000 70 000 200 000 Fuel Consumption Lbs hr 2 8 3 2 3 7 3 2 9 3 Heat Settings 3 Variable Maximum Operating Hours 36 31 Require...

Страница 6: ...from inside the heater See Figure 4 2 Remove all packaging protecting the heater during shipping Retain caps for covering the inlet connector and regulator hose fro storage 3 Attach three 3 screws to...

Страница 7: ...National Standard for Compressed Gas Cylinder Valve Outlets and Inlets Connections A safety relief valve having direct communications with the vapor space of the LP cylinder The heater must operate on...

Страница 8: ...ition turn ON the LP cylinder valve and check for leaks with soap solution Checking For Leaks To check for leaks make up a 50 50 solution of dish soap and water Apply this solution to all gas connecti...

Страница 9: ...SE to close it REM 200V LPC O 1 STOP Read all of the safety information provided with this heater 2 Turn valve on propane cylinder COUNTERCLOCKWISE until fully open 3 Set control valve to LIGHT LOW po...

Страница 10: ...Storage Maintenance Always disconnect the heater from the LP cylinder before putting the heater into storage If for any reason the heater is to be stored indoors the tank MUST be disconnected from th...

Страница 11: ...time for thermocouple to warm up 2 Gas pressure too low 3 Thermocouple needs replacing or loose 4 Control valve damaged 1 Keep Control Valve depressed for at least 30 seconds 2 Check cylinders for ade...

Страница 12: ...R UNATTENDED WHILE BURNING CONNECTED TO A POWER SOURCE OR WHILE CONNECTED TO A FUEL SOURCE 2017 Pinnacle Climate Technologies Inc Convection Heater User s Manual Exploded View 11 Figure 8 REM 80V LPC...

Страница 13: ...condition or not defective the item will be returned freight collect This Limited Warranty is in lieu of all other express warranties Pinnacle Climate Technologies Inc disclaims al warranties for pro...

Страница 14: ...1 Industrial Blvd 101 Sauk Rapids MN 56379 USA Toll Free 866 676 1989 Fax 320 251 2922 Web www remingtonheater com Email info pinnacleclimate com 2017 Pinnacle Climate Technologies Inc...

Страница 15: ...CON EL FABRICANTE PELIGRO DE INCENDIO QUEMADURAS INHALACI N Y EXPLOSI N MANTENGA LOS COMBUSTIBLES S LIDOS COMO MATERIALES DE CONSTRUCCI N PAPEL O CART N A UNA DISTANCIA PRUDENTE DEL CALENTADOR SEG N L...

Страница 16: ...Este calentador est dise ado y aprobado para uso en construcciones de acuerdo con la norma ANSI Z83 7 2011 CSA 2 14 2011 CONSULTE CON LAS AUTORIDADES DE SEGURIDAD DE INCENDIOS DE SU LOCALIDAD SI TIENE...

Страница 17: ...PERMITE PARA Calefacci n temporal de edificios adecuadamente ventilados o estructuras en construcci n modificaci n o reparaci n Proporcione una abertura de al menos tres pies cuadrados 0 28 metros cua...

Страница 18: ...descarga del calentador hacia el tanque de LP a menos que se encuentre a una distancia m nima de 20 pies 6 m del calentador Utilice nicamente el conjunto de regulador y manguera suministrado con este...

Страница 19: ...igura 2 Especificaciones N de modelo REM 80V LPC O REM 200V LPC O BTU 60 000 70 000 80 000 70 000 200 000 Consumo de combustible Lb h 2 8 3 2 3 7 3 2 9 3 Ajustes de calor 3 Variable Horas m ximas de f...

Страница 20: ...ci n al calentador durante el transporte Conserve las tapas que cubren el conector de entrada y lamanguera del regulador para cuando guarde la unidad 3 Fije 3 tres pernos en los orificios de la hilera...

Страница 21: ...caci n de la Norma Nacional Americana para la conexi n de entradas y salidas de v lvulas de tanques de gas comprimido Una v lvula de escape de seguridad con comunicaci n directa con el espacio de vapo...

Страница 22: ...gado abra la v lvula del tanque de LP y revise que no haya fugas usando una soluci n de jab n Inspecci n de fugas Para verificar si hay fugas prepare una soluci n mitad detergente para platos y mitad...

Страница 23: ...la REM 200V LPC O 1 ALTO Lea toda la informaci n de seguridad que acompa a a este calentador 2 Gire la v lvula del tanque de propano hacia la IZQUIERDA hasta abrirla completamente 3 Ponga la v lvula d...

Страница 24: ...con ventilaci n inadecuada Almacenamiento Mantenimiento Antes de almacenar el calentador siempre desconecte el calentador del tanque de LP Si por cualquier raz n ha de almacenarse el calentador en un...

Страница 25: ...ara que se caliente el termopar 2 Muy poca presi n de gas 3 El termopar est flojo o debe reemplazarse 4 V lvula de control da ada 1 Mantenga presionada la v lvula de control al menos 30 segundos 2 Com...

Страница 26: ...S EST ENCENDIDO O MIENTRAS EST CONECTADO A UNA FUENTE DE ALIMENTACI N O A UNA FUENTE DE COMBUSTIBLE 2017 Pinnacle Climate Technologies Inc Manual del usuario del calentador de convecci n Vista detalla...

Страница 27: ...iento o que no est defectuoso se devolver el art culo con el flete por cobrar Esta Garant a Limitada reemplaza a todas las dem s garant as expresas Pinnacle Climate Technologies Inc se desiste de toda...

Страница 28: ...dustrial Blvd 101 Sauk Rapids MN 56379 EE UU Llamada sin costo 866 676 1989 Fax 320 251 2922 Web www remingtonheater com Correo electr nico info pinnacleclimate com 2017 Pinnacle Climate Technologies...

Отзывы: