Connecting the PSSu system
Installation Manual PSSuniversal
21262-EN-07
47
Mounting rail
Earthing terminal
Head module
6.4
Separation of supply
When used with the relevant base module, any electronic supply voltage module is suitable
to separate supplies and form supply groups.
To separate supplies, the supply (periphery supply and C-rail supply) to the preceding (left-
hand) modules is disconnected and a new supply provided for subsequent (right-hand)
modules.
With a new supply group it is also possible to refresh the module supply by providing a new
supply voltage. The 0 V supply on the module supply is never interrupted, but is always
looped through across the whole module bus.
You should always refer to the description of the relevant electronic supply voltage module.
The following modules are suitable for separating supplies, for example:
Electronic module
Base module
Module supply
Periphery supply
and C-rail
PSSu E F PS
PSSu BS-R 1/8 S
PSSu BS-R 1/8 C
Refreshing (new supply
voltage is provided, 0 V
supply is not interrupted).
Supply of the left-hand mod-
ules is interrupted and a new
supply is provided for the
right-hand modules.
PSSu E F PS1
PSSu BS-R 2/8 S
PSSu BS-R 2/8 C
PSSu E F PS-P
PSSu BS 1/8 S
PSSu BS 1/8 C
No refreshing (5 V is not
separated).
PSSu E F BSW
PSSu BS 2/8 S
PSSu BS 1/8 C