Programming device interface RS 485
If you need to cover longer distances between the programming device
and PSS (from approx. 15 m), use the RS 485 interface on the PSS.
If the programming device has no RS 485 interface, connect the RS 485
interface on the PSS to the RS 232 interface on the programming device
via the C-PC-PAP-2 interface adapter (order no. 305 155).
To connect the PSS to the programming device or to the interface adapter,
you will need a cable with a layout as shown in Fig. 8-3. This cable is
available under order number 374 205. It contains all the necessary links.
Fig. 8-3: RS 485 connection cable from the PSS to the interface adapter or
programming device, with links to activate the terminating resistors
PSS
(Female 9-pin D-Sub connector)
Interface adapter
or
programming device
(Female 9-pin D-Sub connector)
1
R1
2
B
3
R2
4
GND 5
6
A
7
R3
8
9
1
2 R1
3 B
5 GND
6
7 A
8 R3
9
4 R2
Screening
Содержание PSS 3075-3 Series
Страница 1: ...Programmable control systems PSS PSS 3075 3 Series Operating Manual Item No 21 071 10 ...
Страница 13: ...2 3 Operating Manual PSS 3075 3 Series Notes ...
Страница 28: ...Overview 2 18 Operating Manual PSS 3075 3 Series Notes ...
Страница 46: ...Installation 5 6 Operating Manual PSS 3075 3 Series Notes ...
Страница 72: ...Wiring the Inputs and Outputs 7 22 Operating Manual PSS 3075 3 Series Notes ...
Страница 86: ...Operation and Maintenance 9 6 Operating Manual PSS 3075 3 Series Notes ...
Страница 94: ...Technical Details 10 8 Operating Manual PSS 3075 3 Series Notes ...
Страница 98: ...Appendix 11 4 Operating Manual PSS 3075 3 Series Notes ...