Wiring the Inputs and Outputs
7-12
Operating Manual: PSS 3075-3 Series
Example: Dual-channel, failsafe input device, with test pulse
Features:
• Depending on the application area and its respective regulations, this
connection diagram is suitable for applications up to category 4 in
accordance with EN 954-1.
• This type of connection is mainly used for signal inputs with infrequent
operation.
• The operating system will detect all shorts between contacts and short
circuits to L+ and L-.
• Short circuits across the contact can be detected via the feasibility check
in the user program.
• The test pulse must be allocated to the input in the system software’s
PSS Configurator (e.g. PSS WIN-PRO).
• On input devices with identical channels, each channel should be given a
separate test pulse. This will ensure that all short circuits are detected,
with the exception of short circuits which short out the input device (cable
from the signal to the input device and cable from the input device to the
input).
• Cable runs: 200 m;
With 1 kOhm resistance parallel to input: max. 800 m
Содержание PSS 3075-3 Series
Страница 1: ...Programmable control systems PSS PSS 3075 3 Series Operating Manual Item No 21 071 10 ...
Страница 13: ...2 3 Operating Manual PSS 3075 3 Series Notes ...
Страница 28: ...Overview 2 18 Operating Manual PSS 3075 3 Series Notes ...
Страница 46: ...Installation 5 6 Operating Manual PSS 3075 3 Series Notes ...
Страница 72: ...Wiring the Inputs and Outputs 7 22 Operating Manual PSS 3075 3 Series Notes ...
Страница 86: ...Operation and Maintenance 9 6 Operating Manual PSS 3075 3 Series Notes ...
Страница 94: ...Technical Details 10 8 Operating Manual PSS 3075 3 Series Notes ...
Страница 98: ...Appendix 11 4 Operating Manual PSS 3075 3 Series Notes ...