PNOZ X2.1C
Operating Manual PNOZ X2.1C
1003973-EN-07
9
Timing diagram
[1]
[2]
Legend
}
Power: Supply voltage
}
Start: Start circuit
}
Input: Input circuit
}
Output safe: Safety contacts
}
[1]: Automatic start
}
[2]: Manual start
}
a: Input circuit closes before start circuit
}
b: Start circuit closes before input circuit
}
t
1
: Switch-on delay
}
t
2
: Delay-on de-energisation
}
t
3
: Recovery time
Installation
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}
When installed vertically: Secure the unit by using a fixing element (e.g. retaining
bracket or end angle).
Wiring
Please note:
}
Information given in the "
Technical details [
13]
" must be followed.
}
The outputs 13-14, 23-24 are safety contacts.
}
To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details [
13]
).
}
Calculation of the max. cable length l
max
in the input circuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see
Technical details [
13]
)
R
l
/ km = cable resistance/km
}
Use copper wire that can withstand 60/75 °C.