PNOZ X2.1C
Operating Manual PNOZ X2.1C
1003973-EN-07
7
Unit features
}
Positive-guided relay outputs:
– 2 safety contacts (N/O), instantaneous
}
Connection options for:
– E-STOP pushbutton
– Safety gate limit switch
– Start button
}
LED display for:
– Supply voltage
– Switch status of the safety contacts
Safety features
The safety relay meets the following safety requirements:
}
The circuit is redundant with built-in self-monitoring.
}
The safety function remains effective in the case of a component failure.
}
The correct opening and closing of the safety function relays is tested automatically in
each on-off cycle.
Block diagram/terminal configuration
PNOZ X2.1C
A1
14
S33 S34
S12
13
23
24
POWER
CH. 1
CH. 2
14
24
13
23
A2
S22
S21
S11
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)