![Pilz PNOZ m ES EtherNet/IP Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/pilz/pnoz-m-es-ethernet-ip/pnoz-m-es-ethernet-ip_operating-manual_1556459009.webp)
Safety
Operating Manual PNOZ m ES EtherNet/IP
1003387-EN-05
9
3
Safety
3.1
Intended use
The fieldbus module PNOZ m ES EtherNet/IP is an expansion module of the configurable
control system PNOZmulti 2. It is used for communication between the configurable control
system PNOZmulti 2 and EtherNet/IP. EtherNet/IP is designed for fast data exchange at
field level. The expansion module PNOZ m ES EtherNet/IP is a passive subscriber (Ad-
apter) of the EtherNet/IP. The basic functions of communication with EtherNet/IP conform
to IEEE 802.3. The central controller (scanner) reads input information from the slaves and
writes output information to the slaves as part of each cycle. As well as the cyclical transfer
of usable data, the expansion module PNOZ m ES EtherNet/IP can also be used for dia-
gnostic and commissioning functions.
The expansion module may only be connected to a base unit from the PNOZmulti system
(please refer to the document "PNOZmulti System Expansion" for details of the base units
that can be connected).
The configurable small control systems PNOZmulti are used for the safety-related interrup-
tion of safety circuits and are designed for use in:
}
E-STOP equipment
}
Safety circuits in accordance with VDE 0113 Part 1 and EN 60204-1
The expansion module may not be used for safety-related functions.
}
The product PNOZ m ES EtherNet/IP meets the requirements of the standards EN
81-20, EN 81-22 and EN 81-50, harmonised under the Lifts Directive 2014/33/EU, and
the requirements of the standard EN 115-1, harmonised under the Machinery Directive
2006/42/EC.
}
The programmable safety system should be installed in a protected environment that
meets at least the requirements of pollution degree 2.
Example: Protected inside space or control cabinet with protection type IP54 and cor-
responding air conditioning.
The following is deemed improper use in particular
}
Any component, technical or electrical modification to the product,
}
Use of the product outside the areas described in this manual,
}
Use of the product outside the technical details (see
NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product
may cause interference if installed in other environments. If installed in other
environments, measures should be taken to comply with the applicable
standards and directives for the respective installation site with regard to in-
terference.