Commissioning
Operating Manual PNOZ m ES EtherNet/IP
1003387-EN-05
17
or
–
Blow-out fuse, slow, 6A
6.3
Interface assignment
RJ45 socket
8-pin
PIN
Standard
8 1
1
TD+ (T)
2
TD- (Transmit-)
3
RD+ ()
4
n.c.
5
n.c.
6
RD- (Receive-)
7
n.c.
8
n.c.
n.c.: Not connected
6.4
Download modified project to the PNOZmulti system
As soon as an additional expansion module has been connected to the system, the project
must be amended in the PNOZmulti Configurator and downloaded back into the base unit.
Proceed as described in the operating manual for the base unit.
NOTICE
For the commissioning and after every user program change, you must
check whether the safety devices are functioning correctly.
6.5
Set IP address
When setting the IP address, please note:
}
Switch off the supply voltage to the fieldbus module PNOZ m ES EtherNet/IP before
setting the DIP switches.
}
The IP address for the fieldbus module PNOZ m ES EtherNet/IP should not be the
same as the PC's IP address.
The following different options are available for setting the IP address.
Set IP address via DIP switches
IP address is set using the DIP switch on the front of the PNOZ m ES EtherNet/IP:
}
The first three bytes of the IP address are: 192.168.1.
}
Subnet mask: 255.255.255.0.
}
The last byte of the IP address is configured using the DIP switch (value range:
1 ...254).