Function description
Operating Manual PNOZ m ES CC-Link
1003817-EN-02
12
4.3
LED status
The LED status of PNOZmulti 2 can be read out via the following High Byte.
High Byte
Low Byte
Bit no
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
RWr (l+2)
LED Byte
Output data o120 - o127
Bit 5-7: Reserved
The LED status of the base unit PNOZ m B0 can be requested directly as follows
}
Bit 0 = 1: LED OFAULT is lit or flashes
}
Bit 1 = 1: LED IFAULT is lit or flashes
}
Bit 2 = 1: LED FAULT is lit or flashes
}
Bit 3 = 1: LED DIAG is lit or flashes
}
Bit 4 = 1: LED RUN is lit
}
Bit 5-7: Reserved
The LED status of the base unit PNOZ m B1 can be requested directly as follows
}
Bit 0 = 1: LED OFAULT is lit or flashes
}
Bit 1 = 1: LED IFAULT is lit or flashes
}
Bit 2 = 1: LED FAULT is lit or flashes
}
Bit 3 = 1: LED DIAG is lit or flashes
}
Bit 4 = 1: LED RUN FS is lit
}
Bit 5: Reserved
}
Bit 6 = 1: LED RUN ST is lit
}
Bit 7: Reserved
4.4
Access to table segments
The data in the tables can be requested via the following addresses.
Input data
The Master requests a table segment:
High Byte
Low Byte
RWw (l+3)
Segment number
Table number
Output data
PNOZmulti 2 answers as follows:
High Byte
Low Byte
RWr (l+3)
Segment number
Table number
RWr(l+4)
Segment Byte 1
Segment Byte 0
RWr(l+5)
Segment Byte 3
Segment Byte 2
RWr(l+6)
Segment Byte 5
Segment Byte 4