Wiring
Operating Manual PMCprotego S12(C)
1002528EN03
58
6
Wiring
6.1
General wiring guidelines
Inputs
}
Appropriate wiring must be used to exclude short circuits between the inputs or to a
supply line!
}
Signal lines must be shielded.
Outputs
}
If short circuits occur between the cable from the output to the load and a supply line, it
will no longer be possible to switch off the load.
Possible remedy: Exclude the error by using separate multicore cable for supply
voltages
}
Use appropriate wiring to exclude short circuits between the outputs!
}
Signal lines must be shielded.
}
The outputs do not need suppression for inductive loads.
Cable material
}
Use copper wiring.
Please note:
}
Cable cross sections for field connection terminals in mm
2
:
– Digital inputs/outputs, supply voltage: 0.5 (AWG20) ... 1.0 (AWG18), AEH without
plastic collar, in accordance with DIN 46228/1
}
Max. cable lengths
– Supply voltage: Max. 30 m
– Digital inputs and outputs: Max. 30 m