PZE X5
Operating Manual PZE X5
1003301EN05
7
Installation
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail.
}
Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele
ment (e.g. retaining bracket or an end angle).
Wiring
Please note:
}
Information given in the "
" must be followed.
}
The outputs 1314, 2324, 3334, 4344, 5354 are safety contacts.
}
To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details).
}
Calculation of the max. cable runs l
max
in the input circuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see Technical details)
R
l
/ km = cable resistance/km
}
Use copper wire that can withstand 60/75 °C.
}
Sufficient fuse protection must be provided on all output contacts with capacitive and in
ductive loads.
}
Do not switch low currents using contacts that have been used previously with high cur
rents.