PNOZ s1

Operating Manual PNOZ s1 
21393-EN-07

7

}

  Semiconductor output

*Connect together the 0V connections on all the external power supplies

Key

}

  S1: E-STOP pushbutton

}

  S2: Start button

}

 

: Switch operated

}

 

: Gate open

}

 

: Gate closed

Information

If a base unit and a contact expansion module from the PNOZsigma range 
are connected via the connector, no additional wiring is necessary.

Operation

The unit is ready for operation when the Power LED is permanently lit.
LEDs indicate the status and errors during operation:

LED on

LED flashes

Information

Status indicators and error indicators may occur independently. In the case 
of an error display, the "Fault" LED will light or flash (exception: "Supply 
voltage too low"). An LED that is also flashing indicates the potential cause 
of the error. An LED that is lit and is static indicates a normal operating sta-
tus. Several status indicators and error indicators may occur simultaneously.

Содержание 750101

Страница 1: ...PNOZ s1 Operating Manual 21393 EN 07 Safety relays...

Страница 2: ...es may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the s...

Страница 3: ...safety at work and accident prevention Ensure VDE and local regulations are met especially those relating to safety Any guarantee is rendered invalid if the housing is opened or unauthorised modifica...

Страница 4: ...Reset Start S34 Y32 K1 K2 13 23 24 14 Interface expansion unit Centre Front view with cover right Front view without cover Function description Single channel operation no redundancy in the input circ...

Страница 5: ...r of the unit to attach it to a DIN rail 35 mm When installed vertically Secure the unit by using a fixing element e g retaining brack et or end angle Push the device upwards or downwards before lifti...

Страница 6: ...age AC DC Input circuit Input circuit Single channel Dual channel Emergency stop without detection of shorts across contacts Safety gate without detection of shorts across contacts Start circuit feedb...

Страница 7: ...is necessary Operation The unit is ready for operation when the Power LED is permanently lit LEDs indicate the status and errors during operation LED on LED flashes Information Status indicators and...

Страница 8: ...n again change unit if neces sary Power Diagnostics Supply voltage too low Remedy Check the supply voltage Faults malfunctions Contact malfunctions If the contacts have welded reactivation will not be...

Страница 9: ...hort circuit current IK 1 kA 1 kA Utilisation category In accordance with the standard EN 60947 4 1 EN 60947 4 1 Safety contacts AC1 at 240 V 240 V Max current 3 0 A 3 0 A Min current 0 02 A 0 02 A Ma...

Страница 10: ...ilure typ 30 ms 30 ms With power failure max 40 ms 40 ms Recovery time at max switching frequency 1 s After E STOP 100 ms 100 ms After power failure 100 ms 100 ms Supply interruption before de ener gi...

Страница 11: ...th crimp connec tors no plastic sleeve 0 25 1 00 mm 24 16 AWG 2 core with the same cross sec tion flexible without crimp con nectors or with TWIN crimp con nectors 0 20 1 50 mm 24 16 AWG Torque settin...

Страница 12: ...l to the SIL PL values of the units that are used and may be different We recommend that you use the PAScal software tool to calculate the safety function s SIL PL values Order reference Order referen...

Страница 13: ...raNET p Pilz PIT PMCprotego PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would po...