PNOZ s1

Operating Manual PNOZ s1 
21393-EN-07

8

Status indicators

Power, In1, In2

 

Input circuit is closed.

Out

 

Safety contacts are closed and semiconductor output Y32 carries a high signal.

 

Reset

  

24 V DC is present at S34.

Error indicators

 

Fault

  

Diagnostics: Plug terminator not connected

}

  Remedy: Insert plug terminator, switch supply voltage off and then on 

again.

 

Fault

  

Diagnostics: Internal error, unit defective

}

  Remedy: Switch supply voltage off and then on again, change unit if neces-

sary.

 

Power

  

Diagnostics: Supply voltage too low

}

  Remedy: Check the supply voltage.

Faults - malfunctions

}

  Contact malfunctions: If the contacts have welded, reactivation will not be possible after 

the input circuit has opened.

Technical Details

General

750101

751101

Approvals

CCC, CE, GOST, KOSHA, TÜV, 

cULus Listed

CCC, CE, GOST, KOSHA, TÜV, 

cULus Listed

Electrical data

750101

751101

Supply voltage

Voltage

24 V

24 V

Type

DC

DC

Voltage tolerance

-15 %/+10 %

-15 %/+10 %

Output of external power supply 

(DC)

2,0 W

2,0 W

Residual ripple DC

20 %

20 %

Continuous duty

100 %

100 %

Max. inrush current impulse

Reset circuit

0,20 A

0,20 A

Feedback loop

0,20 A

0,20 A

Содержание 750101

Страница 1: ...PNOZ s1 Operating Manual 21393 EN 07 Safety relays...

Страница 2: ...es may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the s...

Страница 3: ...safety at work and accident prevention Ensure VDE and local regulations are met especially those relating to safety Any guarantee is rendered invalid if the housing is opened or unauthorised modifica...

Страница 4: ...Reset Start S34 Y32 K1 K2 13 23 24 14 Interface expansion unit Centre Front view with cover right Front view without cover Function description Single channel operation no redundancy in the input circ...

Страница 5: ...r of the unit to attach it to a DIN rail 35 mm When installed vertically Secure the unit by using a fixing element e g retaining brack et or end angle Push the device upwards or downwards before lifti...

Страница 6: ...age AC DC Input circuit Input circuit Single channel Dual channel Emergency stop without detection of shorts across contacts Safety gate without detection of shorts across contacts Start circuit feedb...

Страница 7: ...is necessary Operation The unit is ready for operation when the Power LED is permanently lit LEDs indicate the status and errors during operation LED on LED flashes Information Status indicators and...

Страница 8: ...n again change unit if neces sary Power Diagnostics Supply voltage too low Remedy Check the supply voltage Faults malfunctions Contact malfunctions If the contacts have welded reactivation will not be...

Страница 9: ...hort circuit current IK 1 kA 1 kA Utilisation category In accordance with the standard EN 60947 4 1 EN 60947 4 1 Safety contacts AC1 at 240 V 240 V Max current 3 0 A 3 0 A Min current 0 02 A 0 02 A Ma...

Страница 10: ...ilure typ 30 ms 30 ms With power failure max 40 ms 40 ms Recovery time at max switching frequency 1 s After E STOP 100 ms 100 ms After power failure 100 ms 100 ms Supply interruption before de ener gi...

Страница 11: ...th crimp connec tors no plastic sleeve 0 25 1 00 mm 24 16 AWG 2 core with the same cross sec tion flexible without crimp con nectors or with TWIN crimp con nectors 0 20 1 50 mm 24 16 AWG Torque settin...

Страница 12: ...l to the SIL PL values of the units that are used and may be different We recommend that you use the PAScal software tool to calculate the safety function s SIL PL values Order reference Order referen...

Страница 13: ...raNET p Pilz PIT PMCprotego PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would po...

Отзывы: