QUINT4-PS/12-24DC/24DC/1.3/SC
110257_en_00
PHOENIX CONTACT
8/32
Efficiency
24 V DC
typ. 91.7 %
Eta [%]
0
10
20
30
40
50
60
70
80
90
100
0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00
I
Out
[A]
1
1
2
= U
In
:
12 V DC/U
Out
: 24 V DC
= U
In
:
24 V DC/U
Out
: 24 V DC
2
Ambient conditions
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
The ambient temperature (operation) refers to IEC 61010 surrounding air temperature.
Ambient temperature (start-up type tested)
-40 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Installation height
≤ 5000 m (> 2000 m, observe derating)
Vibration (operation)
< 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in
accordance with IEC 60068-2-6)
Shock
18 ms, 30g, in each space direction (according to IEC 60068-
2-27)
Degree of pollution
2
Climatic class
3K3 (in acc. with EN 60721)
Overvoltage category
EN 61010-1
II (≤ 5000 m)
Standards
Electrical safety (of control and regulation devices)
IEC 61010-1
Protective extra-low voltage
IEC 61010-1 (SELV)
Mains variation/undervoltage
EN 61000-4-29
EMC requirements, power plant
EN 61850-3
EN 61000-6-5