QUINT4-PS/12-24DC/24DC/1.3/SC
110257_en_00
PHOENIX CONTACT
5/32
Electric strength of the insulation
A
Type test ( IEC/EN 61010-1 )
2.6 kV DC
Production test
1.3 kV DC
Housing
A
A
Signaling
Input
L
N
(+)
(-)
Output
+
Input current vs. output current
I
In
[A]
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00
I
Out
[A]
1
1
2
= U
In
:
12 V DC/U
Out
: 24 V DC
= U
In
:
24 V DC/U
Out
: 24 V DC
2
Input connection data
Connection method
Screw connection
Conductor cross section, rigid
0.5 mm² ... 2.5 mm²
Conductor cross section, flexible
0.5 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule with plastic
sleeve
0.5 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without
plastic sleeve
0.5 mm² ... 2.5 mm²
Conductor cross section AWG
22 ... 14
Stripping length
8 mm