QUINT4-PS/12-24DC/24DC/1.3/SC
110257_en_00
PHOENIX CONTACT
11/32
Surge voltage load (surge) EN 61000-4-5
Input
0.5 kV (Test Level 3 -
symmetrical)
1 kV (Test Level 3 -
asymmetrical)
1 kV (Test Level 4 -
symmetrical)
2 kV (Test Level 4 -
asymmetrical)
Output
0.5 kV (Test Level 2 -
symmetrical)
1 kV (Test Level 1 -
asymmetrical)
1 kV (Test Level 3 -
symmetrical)
2 kV (Test Level 3 -
asymmetrical)
Signal
0.5 kV (Test Level 2 -
symmetrical)
1 kV (Test Level 1 -
asymmetrical)
1 kV (Test Level 4 -
symmetrical)
2 kV (Test Level 4 -
asymmetrical)
Comments
Criterion B
Criterion A
Conducted interference EN 61000-4-6
Input/Output/Signal
asymmetrical
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
10 V (Test Level 3)
Comments
Criterion A
Criterion A
Power frequency magnetic field EN 61000-4-8
50 Hz , 60 Hz ( 30 A/m )
16.67 Hz , 50 Hz , 60 Hz
( 100 A/m 60 s )
not required
50 Hz , 60 Hz ( 1 kA/m , 3 s )
not required
0 Hz ( 300 A/m , DC, 60 s )
Comments
Criterion A
Criterion A
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station
equipment zone), IEC/EN 61850-3 (energy supply)
CE basic standard
Minimum normative
requirements of
EN 61000-6-2 (CE)
(immunity for industrial
environments)
Higher requirements in
practice (covered)