![Phoenix Contact IOL MA8 PN DI8 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/phoenix-contact/iol-ma8-pn-di8/iol-ma8-pn-di8_user-manual_1551441036.webp)
IOL MA8 PN DI8
34
PHOENIX CONTACT
4022_en_A
Data Storage Config
Storage Contents
Indicates that the data storage for the port is empty or displays the Vendor ID and Product ID of
the data stored on that port.
Automatic Data Storage
Upload Enable
Default:
Off
When this option is initially set to
On
, the IOL MA8 PN DI8 saves the data storage parameters
(if the data storage is empty) from the IO-Link device to the IOL MA8 PN DI8.
Automatic upload occurs when the “Automatic Upload Enable” option is set to
On
and one of
these conditions exists:
–
There is no upload data stored on the gateway and the IO-Link device is connected to the
port.
–
The IO-Link device has the DS_upload bit on (generally because the configuration via
Teach buttons or configuration page has changed).
When a port contains data storage for an IO-Link device and the attached device has a Vendor
and Device ID that do not match, the IO-Link LED on the IOL MA8 PN DI8 flashes red to indicate
a wrong device is attached. In addition, the “IO-Link Diagnostics” page displays
DS: Wrong
Sensor
in the “IO-Link State” field.
Not all device parameters are sent to data storage; this is determined by the IO-Link device
manufacturer.
Automatic Data Storage
Download Enable
Default:
Off
The data storage parameters on the IOL MA8 PN DI8 are downloaded to the connected IO-Link
device if:
–
The “Automatic Download” option is enabled.
–
The data stored on the IOL MA8 PN DI8 port contains the same Vendor ID and Product ID
as the IO-Link device connected to the port.
–
Data storage parameters are also downloaded to the IO-Link device if configuration
changes are made on the device causing the DS_upload bit to turn on and automatic
upload is not enabled.
–
The IO-Link device requests an upload and the “Automatic Upload Enable” option is set to
Off
.
Disable the “Automatic Download” option because the IOL MA8 PN DI8 will reload the data
storage on the port down to the IO-Link device, if configuration parameters on the IO-Link
device have changed and parameters are desired to remain loaded on the IO-Link device.
Data Storage Manual
Ops
The “Manual Data Storage Ops” option provides the following functionality, if data storage is
supported by the IO-Link device.
–
CLEAR: Clears any stored data for an IO-Link device on this port.
–
UPLOAD: Uploads and stores the IO-Link device configuration on the IOL MA8 PN DI8.
–
DOWNLOAD: Downloads the stored IO-Link device configuration from the IOL MA8 PN
DI8 to the IO-Link device attached to this port, if the Vendor ID and Device ID match.
Table 5-5
“IO-Link Settings” page parameters [...]
Field name
Function
Do not enable
Automatic Upload
and
Automatic Download
at the same time.
Содержание IOL MA8 PN DI8
Страница 1: ...User manual UM EN IOL MA8 PN DI8 IO Link to PROFINET and Modbus TCP gateway...
Страница 14: ...IOL MA8 PN DI8 12 PHOENIX CONTACT 4022_en_A...
Страница 18: ...IOL MA8 PN DI8 16 PHOENIX CONTACT 4022_en_A...
Страница 76: ...IOL MA8 PN DI8 74 PHOENIX CONTACT 4022_en_A...
Страница 82: ...IOL MA8 PN DI8 80 PHOENIX CONTACT 4022_en_A...