QUINT4-PS/1AC/24DC/10
107100_en_01
PHOENIX CONTACT
25 / 50
–
Shorten the excess length of the cable binder ends.
–
Then check again that the connection wiring is properly
secured.
Figure 16
Shorten protruding ends of the cable binder
9
Device connection terminal blocks
The AC input and DC output terminal blocks on the front of
the power supply feature screw connection technology. The
signal level is wired without tools by means of Push-in
connection technology.
9.1
Input
The power supply is operated on single-phase AC systems
or two outer conductors of three-phase systems. The power
supply is connected on the primary side via the INPUT L/N/
connection terminal blocks.
Figure 17
Network types
NOTE:
Mechanical damage to the connection
wiring caused by friction
In extreme ambient conditions, e.g.,
strong
vibrations, protect the connection wiring
against mechanical damage using additional
insulation material. The additional insulation
material for protecting the connection wiring is
limited to the area where the cable binders are
attached.
> 100% Boost
> 75%
> 50%
Pout
13
14
Re
m
SG
nd
Out 1
Out 2
DC OK
U
Out
Signal
For the necessary connection parameters for
the connection terminal blocks, refer to the
technical data section.
The power supply is approved for connection
to TN, TT, and IT power grids with a maximum
phase-to-phase voltage of 240 V AC.
L
PEN
L3
L2
L1
+
N
−
iT
N
L
+
L
N
−
TT
PEN
L
+
L
−
N
L
L3
L2
L1
+
N
−
L
N
L3
L2
L1
+
N
−
L
PE
N
L3
L2
L1
+
N
−
TN-C
PEN
L
+
L
N
−
PE
N
L
+
L
N
−
TN-S