QUINT4-PS/1AC/24DC/10
107100_en_01
PHOENIX CONTACT
13 / 50
Surge voltage load (surge) EN 61000-4-5
Input
1 kV (Test Level 3 -
symmetrical)
2 kV (Test Level 3 -
asymmetrical)
3 kV (Test Level 4 -
symmetrical)
6 kV (Test Level 4 -
asymmetrical)
Output
0.5 kV (Test Level 2 -
symmetrical)
0.5 kV (Test Level 1 -
asymmetrical)
1 kV (Test Level 2 -
symmetrical)
2 kV (Test Level 3 -
asymmetrical)
Signal
1 kV (Test Level 2 -
asymmetrical)
4 kV (Test Level 2 -
asymmetrical)
Comments
Criterion B
Criterion A
Conducted interference EN
61000-4-6
Input/Output/Signal
asymmetrical
asymmetrical
Frequency range
0.15 MHz ... 80 MHz
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
10 V (Test Level 3)
Comments
Criterion A
Criterion A
Power frequency magnetic field EN 61000-4-8
50 Hz , 60 Hz ( 30 A/m )
16.7 Hz , 50 Hz , 60 Hz
( 100 A/m 60 s )
not required
50 Hz , 60 Hz ( 1 kA/m , 3 s )
not required
0 Hz ( 300 A/m , DC, 60 s )
Comments
Criterion A
Criterion A
Voltage dips EN 61000-4-11
Input voltage ( 230 V AC , 50 Hz )
Voltage dip
70 % , 25 periods
( Test Level 2 )
70 % , 0.5 / 1 / 25 periods
( Test Level 2 )
Comments
Criterion C
Criterion A: 0.5 / 1 / 25 periods
Voltage dip
40 % , 10 periods
( Test Level 2 )
40 % , 5 / 10 / 50 periods
( Test Level 2 )
Comments
Criterion C
Criterion A
Voltage dip
0 % , 1 period
( Test Level 2 )
0 % , 0,5 / 1 / 5 / 50 / 250
periods ( Test Level 2 )
Comments
Criterion B
Criterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station
equipment zone), IEC/EN 61850-3 (energy supply)
CE basic standard
Minimum normative
requirements of
EN 61000-
6-2 (CE)
(immunity for industrial
environments)
Higher requirements in
practice (covered)