IB IL 24 MUX MA-PAC

82

PHOENIX CONTACT

5981_en_06

A 5.3

Setting the Ethernet converters using software or 

Web-Based Management (WBM)

Assign fixed IP addresses for both FL COM SERVER RS485: 

Click "General Configuration".

Enter the password (default password: private) and confirm the entry by clicking 

"Enter". 

Select "IP" and enter the IP parameters.

Figure A-7

Assigning IP addresses

Confirm the modification of the configuration with "Confirm".

Proceed in the same way for both FL COM SERVER RS485:

Set the parameters of the serial interface. 

Click on "Serial" and set the parameters specified below.

Transmission speed: 7000 bps

Data  bits:  8

Parity:  Even

Stop bits: 1

Figure A-8

Assigning IP addresses

Содержание 2861205

Страница 1: ...User manual Configuring and installing the Inline field multiplexer...

Страница 2: ...02 22 PHOENIX CONTACT 5981_en_06 Configuring and installing the UM DE IB IL 24 MUX MA PAC 06 Designation Order No IB IL 24 MUX MA PAC 2861205 User manual Designation Revision This user manual is valid...

Страница 3: ...nsmission media in the field multiplexer system 20 3 4 2 Supply from a single power source 20 3 4 3 Alarm contact 20 3 4 4 Temperature measurements 21 3 5 Configuration 22 3 5 1 Configuring the fiber...

Страница 4: ...limits 48 7 3 Selecting suitable power supply units 49 7 4 Providing surge protection 50 7 5 Selecting the transmission medium 50 7 6 Determining the transmission time 50 7 7 Installing and configuri...

Страница 5: ...multiplexer settings 73 A 3 3 Configuring modems using software 73 A 3 4 Setting the DIP switches of the modems 75 A 3 5 Configuring the converters 76 A 3 6 Connecting the cables 77 A 4 Transmission o...

Страница 6: ...IB IL 24 MUX MA PAC 6 PHOENIX CONTACT 5981_en_06...

Страница 7: ...e 8 32825 Blomberg GERMANY Should you have any suggestions or recommendations for improvement of the contents and layout of our manuals please send your comments to tecdoc phoenixcontact com This is t...

Страница 8: ...ducts in your specific application in particular with regard to observing the applicable standards and regulations All information made available in the technical data is supplied without any accompan...

Страница 9: ...the field multiplexer in association with Inline Modular IO IL SYS INST UM E Automation terminals of the Inline product range user manual This manual is the generic system manual for Inline and descr...

Страница 10: ...n description Local diagnostic and status indicators Pin assignment terminal point assignment and connection example Programming data configuration data Technical data Package slips A package slip con...

Страница 11: ...such a way that each input terminal is assigned to an output terminal on the other side and vice versa complementary arrangement see Figure 2 1 In addition to the complementary arrangement of I O term...

Страница 12: ...cable the signals are output again through the complementary I O terminals in the opposite station Data is transmitted between two field multiplexer stations over a 2 wire copper cable RS 485 transmis...

Страница 13: ...in the following limits Only the I O terminals from one of the two stations have to be taken into consideration when making the calculation tup n 6 8 ms byte 78 ms m tup Update time for field multiple...

Страница 14: ...t of 2 A at 7 5 V DC in the logic area 4 The field multiplexer can supply a maximum current of 0 5 A at 24 V DC to analog terminals 5 The maximum current for the I O supply is 8 A at US UM and GND tot...

Страница 15: ...ng clamp connections of the Inline connectors In order to implement data transmission over other transmission media additional interface converters from Phoenix Contact must be used see Section Transm...

Страница 16: ...al grounding Ground the field multiplexer additionally through the FE connection to ensure reliable grounding of the station even if the FE spring is dirty or damaged Connect the terminal points for t...

Страница 17: ...ed Stop On Field multiplexer in stop Off Field multiplexer system operating CE Red Configuration Error On Configuration error Off Configuration of both field multiplexers is OK RE Red Remote bus Error...

Страница 18: ...M Figure 3 3 Terminal point assignment 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 1 1 2 1 3 1 4 2 1 2 2 2 3 2 4 4 1 2 3 1 1 1 2 1 3 1 4 2 1 2 2 2 3 2 4 5 9 8 1 A 0 1 9 Table 3 2 Terminal point assignme...

Страница 19: ...the potential jumper 1 3 2 3 GND The reference potential is directly led to the potential jumper and is at the same time ref erence ground for the main and segment supply 1 4 2 4 FE Connection of the...

Страница 20: ...cable jumpers must be inserted for this purpose Figure 7 3 on page 54 3 4 3 Alarm contact The field multiplexer has a floating alarm output Alarm_IN and Alarm_OUT contacts at connector 3 see Figure 3...

Страница 21: ...iplexers You will find MCR temperature measuring transducers that can be used in the field multiplexer system in Section Ordering data on page 65 PT 100 and thermocouple sensors can be connected to th...

Страница 22: ...ter or a slave One field multiplexer station must be configured as the master To do this insert a cable jumper at connector 3 from 1 4 to 2 4 CONFMA see Figure 3 6 on page 22 The second station must b...

Страница 23: ...iplexer station is correctly mounted End clamps fix the station on both sides and keep it from moving from side to side on the DIN rail Phoenix Contact recommends using CLIPFIX 35 5 end clamps Order N...

Страница 24: ...ood contact between the connector and base Do not damage or squeeze the wires Do not strip more than 8 mm off the wires Always connect analog sensors and actuators with shielded twisted pair cables Co...

Страница 25: ...og and digital signals on the field multiplexer Function terminals from the Inline product range e g temperature sensors counters or absolute encoder modules are not permitted on the field multiplexer...

Страница 26: ...IB IL 24 MUX MA PAC 26 PHOENIX CONTACT 5981_en_06...

Страница 27: ...terminals supplied through potential jumpers UL Analog terminal supply provided through the potential jumper UANA UM 24 V main circuit supply The main voltage UM supplies all of the devices connected...

Страница 28: ...age supplies The supply voltage to the sensors and actuators UM US should be installed and protected independently of the field multiplexer supply UMUX In this way the bus continues to run even if som...

Страница 29: ...e power terminal Segment terminal The segment terminal interrupts the potential jumper US of the previous terminal an recreates it segment circuit US To do this the voltage is tapped off from the pote...

Страница 30: ...Electrical isolation Functional earth ground shield FE and FE capacitive shield represent two separate isolated groups The field multiplexer does not have electrical isolation for the I O terminal co...

Страница 31: ...e for shield 3 Area of functional earth ground FE 4 Area of the field multiplexer supply UMUX from which the communications power UL and supply for the analog terminals UANA are generated 5 Area of th...

Страница 32: ...1 Area of remote bus cable 2 Area of functional earth ground FE capacitive for shield 3 Area of functional earth ground FE 4 Area of the field multiplexer supply UMUX from which the communications pow...

Страница 33: ...The voltage UANA is looped through each terminal and is therefore available to the next terminal Figure 4 5 Electrical isolation between field multiplexer and analog module The potential jumpers hatc...

Страница 34: ...rminal is illustrated in Figure 4 6 Connection between the ground of a supply voltage UMUX US or UM and functional earth ground must only be made at one point within the station point A Electrical iso...

Страница 35: ...on Transmission over copper cable on page 67 Rules for laying the remote bus cable are also given there Attention must also be paid to appropriate grounding and shielding measures see Section Groundin...

Страница 36: ...shield are connected The surge arrester should be installed as directly as possible next to the field multiplexer head station The wiring between the field multiplexer and the surge arrester can then...

Страница 37: ...arrester of field multiplexer A and to the TERMITRAB terminal Version 2 not recommended This version is suitable if only a 3 wire cable with no shield is available In this case only the DATA and DATA...

Страница 38: ...T A S h i e l d D A T A F i e l d M u l t i p l e x e r B D A T A G N D D A T A S h i e l d D A T A S u r g e p r o t e c t i o n 8 1 0 4 1 2 7 9 3 1 1 S u r g e p r o t e c t i o n 7 9 3 1 1 8 1 0 4...

Страница 39: ...ing can be implemented for example with the universal USLKG 5 ground terminal block Order No 0441504 see Section 9 2 Ordering data or the CLIPLINE catalog from Phoenix Contact 1 Grounding terminals fo...

Страница 40: ...should be included in the surge protection scheme Because of the mechanical sensitivity of fiber optics only fiber types with a strong cladding around the transmission medium should be used 1 2 1 2 3...

Страница 41: ...ransmission distance Advantages Converter C Modem M required Copper cable Up to 12 km Use of existing data cables No Fiber optic cable From 100 m up to 45 km Not sensitive to surge voltages e g out do...

Страница 42: ...ST Y 0 8 Lg Telephone line 0 8 mm 4 9 36 6 10 100 LiYCY TP 2x2x1 Data cable shielded 1 mm2 5 3 20 20 0 65 160 1 The value specified is to be considered as a guide value only Shorter and longer distan...

Страница 43: ...ignals are to be transmitted from a control room to a pumping station over a distance of 3 2 km An existing copper cable can be used as the transmission medium 4 digital input signals 2 digital output...

Страница 44: ...F IB IL 24 SAFE 1 PAC IB IL DO 1 AC PAC 1 1 1 1 1 1 1 1 IB IL 24 DO 2 2 2 2 2 2 1 1 2 2 IB IL 24 DO 4 4 IB IL 24 DO 8 8 IB IL 24 DO 16 16 IB IL 24 DO 32 HD 32 IB IL 24 230 DOR 1 W PC PAC 1 1 1 1 1 1 1...

Страница 45: ...B IL 24 DO 32 HD NPNPAC IB IL AI 2 SF IB IL AI 2 SF PAC IB IL AO 2 U BP IB IL AO 2 U BP PAC IB IL AI 2 SF 230 PAC IB IL AO 2 U BP ME IB IL AI 2 SF ME Table 7 2 Possible combinations of analog I O term...

Страница 46: ...IX CONTACT 5981_en_06 Figure 7 1 Combining DO 1 and DI 2 terminals 1 2 1 D D O 1 1 2 1 D D O 1 5 9 8 1 A 0 2 1 1 2 1 D D O 1 1 2 1 D D O 1 1 2 1 2 D D I 2 1 2 1 2 D D I 2 1 2 1 2 D D I 2 D O 1 D O 1 D...

Страница 47: ...r 3 wire technol ogy Or IB IL 24 DI 2 PAC 2 Connection of 4 digital input signals using 4 wire technology 3 IB IL 24 DO 2 2A PAC 1 Connection of 2 digital output signals 4 IB IL AI 2 SF PAC 1 Connecti...

Страница 48: ...imum 4 maximum 4 maximum Number of signals 512 maximum 4 DI 2 DO 2 AI 4 2 2 16 38 4 DO 2 DI 2 AO 4 2 2 16 38 Current at UL 2 A maximum 0 165 A see Table 7 6 0 159 A see Table 7 7 Current at UANA 0 5 A...

Страница 49: ...r terminals that draw their current from separate power supplies Example project There is no electrical isolation required between logic and I O in the example project The master and the slave station...

Страница 50: ...a copper remote bus cable is selected for the example 7 6 Determining the transmission time The formulas to calculate the transmission time are given in Section Transmission time on page 13 The examp...

Страница 51: ...system is not ready for operation For later extensions insert digital terminals before analog terminals FE connection To ensure reliable grounding of the field multiplexer station ground the field mu...

Страница 52: ...1 2 3 4 S T C E U L R E L E U S U M M U X 1 2 1 2 3 4 1 2 3 4 1 2 D D O 2 1 2 1 2 3 4 1 2 3 4 1 2 D D I 2 M U X D I 4 D I 2 D O 2 A I 2 1 2 1 2 3 4 1 2 3 4 D A I 2 C o p p e r c a b l e 3 8 k m 1 2 1...

Страница 53: ...ransmission over telephone line modem on page 72 Section Transmission over Bluetooth wireless on page 79 or Section Transmission over Ethernet COM SERVER on page 81 Configure master and slave One fiel...

Страница 54: ...has a floating alarm output Alarm_IN and Alarm_OUT contacts at connector 3 that allows to indicate operating errors remotely The contact is normally open but it is closed in the event of an error and...

Страница 55: ...nstallation Step Reference to documentation 1 Are all the Inline terminals approved for use in the field multiplexer system Section Devices permitted in a field multiplexer station on page 43 2 Is the...

Страница 56: ...ion of the local field multiplexer station Making contact with the opposite station and exchange of configuration data and status messages Comparing of the two configurations Opening the alarm relay a...

Страница 57: ...found when restarting remote bus and local bus operating correctly and correctly configured for each other data transmission is resumed automatically If an error is found the field multiplexers will...

Страница 58: ...ications power and interface supply ST Red Stop Field multiplexer is in the stop state CE Red Configuration Error RE Red Remote Bus Error LE Red Local Bus Error Error on the local bus of this field mu...

Страница 59: ...the LEDs on the devices D LED flashing see terminal specific data sheets or Section Localizing errors on a field multiplexer station on page 60 8 Local bus configuration not permitted Check local bus...

Страница 60: ...ion 1 IB IL 24 MUX MA PAC 2 IB IL 24 DI 4 PAC 3 IB IL 24 DI 2 PAC 4 IB IL 24 DO 2 2A PAC 5 IB IL 24 AI 2 PAC When the system is operating correctly the green LEDs on the field multiplexer and the othe...

Страница 61: ...nal 4 IB IL 24 DO 2 2A Effect field multiplexer UL LED and LE LED are on see Table 8 3 no 12 Opposite station UL LED is on LE LED is flashing see Table 8 3 no 13 Terminal 4 D LED flashes at 2 Hz Other...

Страница 62: ...s e l f t e s t S e l f t e s t s u c c e s s f u l E r r o r a c c o r d i n g t o L E D c o d e s e e T a b l e 8 2 L o c a l b u s s t a r t u p R e m o t e b u s s t a r t u p S t a r t u p s u c...

Страница 63: ...o n O K E r r o r a c c o r d i n g t o L E D c o d e s e e T a b l e 8 2 S T L E D o n a l l o t h e r s o f f a l a r m r e l a y c l o s e d d i g i t a l o u t p u t s r e s e t a n a l o g o u t...

Страница 64: ...IB IL 24 MUX MA PAC 64 PHOENIX CONTACT 5981_en_06...

Страница 65: ...ption Type Order No Pcs Pkt Keying profile CP MSTB see COMBICON catalog 2742683 100 Zack marker strip to label the terminals ZBF 6 see CLIPLINE catalog ZBF 12 see CLIPLINE catalog DIN EN 50022 DIN rai...

Страница 66: ...ooth See INTERFACE catalog See also Section Transmission over Bluetooth wireless on page 79 Ethernet converter for data transmission over Ethernet See INTERFACE catalog See also Section Transmission o...

Страница 67: ...d additionally be a twisted pair Laying the remote bus cable When laying the remote bus cable note the following Do not lay signal and bus cables in parallel to power cables If possible lay remote bus...

Страница 68: ...1 FO RS 485 FO RS 485 FO DATA GNDDATA SHD DATA D B GND SHD D A D B GND SHD D A CONVERTER CONVERTER A A 5981B031 MUX 2 DATA GNDDATA SHD DATA MUX IB IL 24 MUX MA PAC A Adapter cable IB IL MUX CAB PSI CO...

Страница 69: ...atalog from Phoenix Contact Table A 2 Fiber optic converters with one fiber optic interface Order Designation Order No Cable type used Distance PSI MOS RS485W2 FO 660 E 2708313 POF Up to 100 m HCS PCF...

Страница 70: ...ettings according to the application Table A 4 Configuration of the converters using DIP switches DIP switch Position Meaning 1 OFF Transmission speed 75 kbps 2 ON 3 ON 4 OFF 5 OFF Telegram length 11...

Страница 71: ...ction between converter and field multiplexer Converter PSI MOS RS485W2 FO Field multiplexer IB IL 24 MUX MA PAC Terminal point Signal Connector 1 Terminal point Signal Color 5 Shield 1 4 2 4 Shield 6...

Страница 72: ...D D A CONVERTER A RS 485 D B GND SHD D A CONVERTER A MUX 2 DATA GNDDATA SHD DATA GND TxD RxD CTS RS 232 GND TxD RxD CTS RS 232 MUX IB IL 24 MUX MA PAC A Adapter cable CONVERTER RS232 RS485 converter P...

Страница 73: ...field multiplexer in Section Terminal point assignment on page 18 Connect the modem and the PC via a serial 1 1 cable and supply it with 24 V DC Start the PSI MODEM CONF configuration software on the...

Страница 74: ...in the pulldown menu or click the Edit profile button Set the following parameters in the Modem Configuration window and confirm the settings with OK DTR Signal Ignore DTR Signal Flow Control NONE Er...

Страница 75: ...river into the slot at the bottom of the cover and lever it open Set the DIP switches of the modem according to Table A 8 Close the protective cover and execute a cold start 24 V OFF and ON Table A 7...

Страница 76: ...e ON position Set the DTE DCE slide switch to DCE Push the housing cover into the base element until it locks Second converter Enter the settings for the second RS 232 RS 485 converter as well Both co...

Страница 77: ...example is shown in Figure A 4 Table A 10 Connection between converter and modem Converter PSM ME RS232 RS485 P Modem PSI DATA FAX MODEM RS232 Signal SUBCON 9 F SH Pin SUBCON 9 F SH Pin Signal Shield...

Страница 78: ...2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 ST CE UL RE LE US UM MUX 1 2 1 2 3 4 1 2 3 4 1 2 D DI2 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 D D...

Страница 79: ...GNDDATA SHD DATA BT BT Bluetooth MUX IB IL 24 MUX MA PAC A Adapter cable CONVERTER Bluetooth converter PSI WL RS232 RS485 BT Bluetooth Bluetooth connection ACHTUNG Malfunction In combination with the...

Страница 80: ...o jumper must be installed from 1 1 to 2 1 CONFFO on connector 1 of both field multiplexers You will find the additional terminal point assignment of the field multiplexer in Section Terminal point as...

Страница 81: ...HD DATA D B GND SHD D A D B GND SHD D A CONVERTER CONVERTER A A 5981A042 MUX 2 DATA GNDDATA SHD DATA LAN WAN MUX IB IL 24 MUX MA PAC A Adapter cable CONVERTER Ethernet converter For example Phoenix Co...

Страница 82: ...t password private and confirm the entry by clicking Enter Select IP and enter the IP parameters Figure A 7 Assigning IP addresses Confirm the modification of the configuration with Confirm Proceed in...

Страница 83: ...tion mode and make the following settings Figure A 9 UDP settings of COM SERVER 1 Figure A 10 UDP settings of COM SERVER 2 Confirm the modification of the configuration with Confirm Own UDP Port Own U...

Страница 84: ...rd private and confirm the entry by clicking Confirm Figure A 11 Save the settings and reboot the FL COM SERVER RS485 Confirm your settings with Confirm The FL COM SERVER RS485 restarts with the saved...

Страница 85: ...Yellow Data N A 8 2 2 Data Green 5981A045 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 4 ST CE UL RE LE US UM MUX 1 2 1 2 3 4 1 2 3 4 1 2 D DO2 1 2 1 2 3 4 1 2 3 4 1 2...

Страница 86: ...IB IL 24 MUX MA PAC 86 PHOENIX CONTACT 5981_en_06...

Страница 87: ...Fiber optic converter 68 Field multiplexer Alarm contact 54 Configuration and installation 43 Connecting the remote bus 53 Connection to FE 15 Connections 15 Copper transmission mode 22 Diagnostic ind...

Страница 88: ...S485 P 72 R RS 232 RS 485 converter 72 S Shielding 24 Concept 24 Startup 55 Supply terminal 25 Surge protection 35 50 Control cabinet 35 Fiber optic operation 40 Power supply 35 39 Remote bus cable 35...

Отзывы: