IB IL 24 MUX MA-PAC
22
PHOENIX CONTACT
5981_en_06
3.5
Configuration
The field multiplexer does not require any configuration software. It is configured with cable
jumpers on the connectors.
3.5.1
Configuring the "fiber optics (FO)" transmission mode
If you want to implement fiber optic data transmission, insert a cable jumper at connector 1
from 1.1 to 2.1 (CONF
FO
) (see Figure 3-6 on page 22).
Set the required fiber optic converters to a transmission rate of 75 kbaud and a character
length of 11 bits (see also Section “Transmission over fiber optics” on page 68).
3.5.2
Configuring the station as a master or a slave
One
field multiplexer station
must
be configured as the master. To do this, insert a cable
jumper at connector 3 from 1.4 to 2.4 (CONF
MA
) (see Figure 3-6 on page 22).
The
second
station
must
be configured as a slave. It must not have a wire jumper at
connector 3 from 1.4 to 2.4.
3.6
Connection example
Figure 3-6
Typical connection of the cables to the field multiplexer
ACHTUNG: Malfunction
Ensure that the same transmission mode (copper/fiber optics) is always set on the field
multiplexer station and the opposite station.
1
2
1
2
3
4
1
2
3
4
1
2
1
2
3
4
1
2
3
4
1
2
1
2
3
4
1
2
3
4
1
2
1
2
3
4
1
2
3
4
ST
CE
UL
RE
LE
US
UM
MUX
Possible 24 V
segment supply
(U )
S
5985A008
Alarm signals
24 V main
supply (U )
M
Connector 1
2
3
4
24 V field multiplexer
supply (U
)
MUX
ALARM
+
-
+
-
Remote bus
+
-
Master
FO
Содержание 2861205
Страница 1: ...User manual Configuring and installing the Inline field multiplexer...
Страница 6: ...IB IL 24 MUX MA PAC 6 PHOENIX CONTACT 5981_en_06...
Страница 26: ...IB IL 24 MUX MA PAC 26 PHOENIX CONTACT 5981_en_06...
Страница 64: ...IB IL 24 MUX MA PAC 64 PHOENIX CONTACT 5981_en_06...
Страница 86: ...IB IL 24 MUX MA PAC 86 PHOENIX CONTACT 5981_en_06...