Electrical isolation: Other
Other electrical isolation depends on how the supply voltages are provided. For instance,
electrical isolation can be provided by inserting a new 24 V supply using a power terminal.
During this process the 24 V power supply units on the low voltage side must not be
connected to one another.
One method of electrical isolation using a power terminal is illustrated in Figure 4-6.
Connection between the ground of a supply voltage (U
MUX
, U
S
or U
M
) and functional earth
ground must only be made at one point within the station (point A). Electrical isolation is lost
if several grounds are connected to functional earth ground.
Figure 4-6
Creating electrical isolation
Electrically isolated areas within the station:
1
Bus logic of the complete field multiplexer station
2
I/O (outputs)
3
I/O (inputs)
1
2
1
2
1
2
1
2
2
1
2
1
2
1
2
1
2
3
1
2
1
2
1
2
ST
CE
UL
RE
LE
US
UM
MUX
+
-
+
-
1
2
UM
PWR IN
+
-
A
1
IBS IL 24 MUX MA-PAC
IB IL 24 PWR IN-PAC
DO
DI
5981B010
1
2
U
MUX
U /U
M
S
U /U
M
S