IB IL 24 MUX MA-PAC
42
PHOENIX CONTACT
5981_en_06
Table 6-3
Typical copper cables
Cable type
Theoretical
range
1
[km]
Cable parameters
Cable
resistance
[
/km]
Cross
resistance
[G
* cm]
Inductance
[mH/km]
Operating
capacitance
[nF/km]
J-Y(ST)Y ... 0,6 Lg
(Telephone line, 0.6 mm)
3.4
65
10
–
120
J-Y(ST)Y ... 0,8 Lg
(Telephone line, 0.8 mm)
4.9
36.6
10
–
100
LiYCY(TP) 2x2x1
(Data cable, shielded, 1 mm
2
)
5.3
20
20
0.65
160
1
The value specified is to be considered as a guide value only. Shorter and longer distances are possible depending on the surrounding conditions.
Please refer to the Appendix A “Technical appendix: The field multiplexer with different
transmission media” for information on component wiring and configuration of the
converters (and modems when using a telephone line).