Phoenix Contact 28 64 21 5 Скачать руководство пользователя страница 22

Page 10

5

Parameter setup

The parameters have to be set up before
putting the unit into operation.
– Input parameter
The parameters of the scaling slope must
be set up depending on the sensor used.
– Scaling scope
The correspondence between the input
signal and the displayed value is given by
the scaling slope. The scaling slope is set
up by entering pairs of values.
– Totalizer
The decimal point, the factor of the meas-
uring unit, and the scaling of displaying
the total value calculated by the unit must
be set up.

– Alarms/outputs
Either none, one or two alarm values can
be active. Hysteresis and output parame-
ters are also set up. If the set-point is ex-
ceeded, a signal will be sent out at the
corresponding output and the correspon-
ding LED will be switched on.
The alarms themselve are set up in the
operating mode!

– Mains Hum Filter
To reduce operational interference
caused by the 50/60 Hz mains supply you
can choose the local mains frequency.

5.1

Parameter Mode

To put the unit into set-up mode
1. keep the 

key pressed

2. connect the unit with the power supply
3. When the display shows 

release the key.

Getting acquainted with the displays and
keys
The selection or the settings can be run
through as often as required thanks to the
step-through programming method
Menu item:
The display alternates every 2 seconds
between

Entering into the menu:
Either a selection has to be made or a
value has to be set up.
Press the 

key . The display stops 

alternating.
– Making a selection:
Pressing the

key displays all the pos-

sible settings one after the other.
– Enter the selection:
Press the 

key. The selected param-

eter will be stored. The next menu item 
appears
– Entering a value:
The flashing digit indicates that it is en-
abled for entry.
Press the 

key, the number will be 

incremented.

Menu

<–>

Selection

Page 11

Where negative values are permitted, the
highest digit will switch from “9” to”–”
and only then to “0”. 
Press the  

key to switch to the next

digit.

Enter value: Press the  

key,  the

value will be stored. The next menu item 
appears.

5.2 Input Parameters for Instantaneous
value
All set-ups related to the input signal and
the corresponding displayed value are
carried out here.  The displayed value 

is displayed from the input signal via the
scaling slope.

5.2.1Select range for the input signal

Menu

<–>

Selection

Display range

(–0,500 ... 10,500)

2 ... 10 V

(01,500 ... 10,500)

-10 ... +10 V

(–10,500 ... 10,500)

0 ... 20 mA

(–01,000 ... 21,000)

4 ... 20 mA

(03,000 ... 21,000)

0 ... 10 V

(–0,500 ... 10,500)

5.2.2Set the decimal point for the Instantaneous value

Menu

<–>

Selection

Range

–19999 ... 99999

0,0

–1999,9 ... 9999,9

0,00

–199,99 ... 999,99

0,000

–19,999 ... 9999,9

0,0000

–1,9999 ... 9,9999

The position of the decimal
point has no influence on
the measuring accuracy.
The maximum display value
must be within the display
range.  After the decimal
point is set up, the leading
zeros in the display will be
suppressed.

press key 

to accept the selection

press key 

to accept the selection

english

Содержание 28 64 21 5

Страница 1: ...Voltage signals with Adding Counter and 2 Limits C Co on nt tr r l le eu ur r d de e p pr ro oc ce es ss s pour signaux de courant de tension avec totalisateur et 2 valeurs limite C Co on nt tr ro ol...

Страница 2: ...Werkeinstellung factory preset r glage usine...

Страница 3: ...talisatorwert 18 5 4 3 R ckstellung des Totalisatorwert 19 5 5 Grenzwerte Grenzwert Ausg nge 5 5 1 Grenzwert 1 Grenzwert Ausgang 1 20 5 5 1 1 Grenzwert 1 aus einschalten 20 5 5 1 2 Grenzwert 1 zuordne...

Страница 4: ...anwendungs spezifische Bestimmungen 6 Die Digitalanzeige ist nicht geeingent f r den explosionsgesch tzten Bereich und den Einsatzbereichen die in EN 61010 Teil 1 ausgeschlossen sind 7 Die Digitalanz...

Страница 5: ...hrungen Spannungsausgang 10 V DC 2 30 mA und Spannungsausgang 24 V DC 15 50 mA Bei DC Ausf hrungen nur Spannungsausgang 10 V DC 2 30 mA Die Hilfsenergieversorgungen sind von den Eing ngen den Grenzwe...

Страница 6: ...ingang X2 X1 X2 X2 Seite 9 deutsch 1 2 3 4 5 6 7 8 9 10 11 1 1 1 9 GND3 f r Uout 10 Uout 10 V 30 mA 11 Uout 24 V 50 mA nur bei Versorgung mit 90 260 V AC 8 MP Input Reset Grenzwert Latch Display Hold...

Страница 7: ...Men punkt Entweder ist eine Auswahl zu treffen oder ein Wert ist einzustellen Taste dr cken Das Wechseln in der Anzeige stoppt Eine Auswahl treffen Mit der Taste werden alle M glich keiten nacheinande...

Страница 8: ...Signal den hier eingestellten Wert wird im Wechsel mit dem aktuellen Messwert an gezeigt Overflow Ist das Mess Signal gr er als 11 00 V bzw 21 5 mA wird dies in der An zeige durch signalisiert Men Au...

Страница 9: ...llt Danach wird der Anzeigewert f r den Be ginn der Kennlinie eingestellt Beispiel 250 0 Stelle w hlen Ziffer einstellen 5 3 3 Die zweite St tzstelle definieren Eingangswert einstellen Men Auswahl Bei...

Страница 10: ...44 442 Der angezeigte Totalisatorwert wird aus dem Ergebnis im Totalisator gebildet indem der Dezimalpunkt in der Anzeige nach Bedarf gesetzt wird Beachte Zur Optimierung der Genauigkeit empfielt es s...

Страница 11: ...Dezimalstelle w hlen Wert einstellen Mit dem Faktor k nnen Umrechnungen in andere Ma einheiten vorgenommen wer den mit bernehmen mit bernehmen Seite 19 deutsch Skalierung einstellen Men Auswahl 100 10...

Страница 12: ...ann entweder dem Totali satorwert oder dem aktuellen Messwert zugeordnet werden mit bernehmen mit bernehmen mit bernehmen Seite 21 deutsch 5 5 1 4 Hysterese f r Grenzwert 1 Hysterese bedeutet hier Dif...

Страница 13: ...play Hold Funktion ist ausgeschaltet Reset sowohl manuell als auch elektrisch Grenzwert Ausgang kann manuell ber die rote Taste oder elektrisch ber einen Reset Impuls am MP Eingang zur ckgesetzt werde...

Страница 14: ...die rote Taste oder elektrisch ber einen Reset Impuls am MP Eingang zur ckgesetzt werden Wenn als angew hlte Funktion angezeigt wird kann der Grenzwert Ausgang nur manuell und oder elektrisch zur ckge...

Страница 15: ...rung von netzseitigen und umgebungsbedingten St rungen Netzbrumm mu das Ger t auf die lokale Netzfrequenz eingestellt werden Men Auswahl Lokales Netz mit 60 Hz Lokales Netz mit 50 Hz mit bernehmen mit...

Страница 16: ...emessen Das Mess Signal ist gr er 11 0 V bzw gr er als 21 5 mA Seite 29 deutsch aktueller Messwert MIN Wert wenn aktiviert MAX Wert wenn aktiviert Grenzwert 1 wenn aktiviert Grenzwert 2 wenn aktiviert...

Страница 17: ...talisators R cksetzen ist nur m glich wenn der MP Eingang f r die Funktion R cksetzen para metriert wurde Je nach Einstellung erfolgt das R ckset zen manuell mit der roten Taste und oder elektrisch mi...

Страница 18: ...talizer 18 5 4 2 2 Overall scaling for the total value 18 5 4 3 Resetting the Total value 19 5 5 Alarms Alarm Outputs 5 5 1 Alarm 1 Output 1 20 5 5 1 1 Alarm 1 off on 20 5 5 1 2 Select threshold 1 20...

Страница 19: ...or user specific regu lations 6 The digital display is not intended for use in areas with risks of explosion and in the branches excluded by the standard EN 61010 Part 1 7 The digital display shall on...

Страница 20: ...oltage output 24 V DC 15 50 mA DC models only voltage output 10 V DC 2 30 mA The auxiliary power supply is galvanically isolated from the inputs and outputs Page 7 2 3 Mechanical Data Housing Housing...

Страница 21: ...ltage input X2 X1 X2 X2 Page 9 1 2 3 4 5 6 7 8 9 10 11 1 1 1 9 GND3 for Uout 10 Uout 10 V 30 mA 11 Uout 24 V 50 mA only for power supply 90 260 V AC 8 MP Input Reset Alarm Latch Display Hold Reset Tot...

Страница 22: ...nu Either a selection has to be made or a value has to be set up Press the key The display stops alternating Making a selection Pressing the key displays all the pos sible settings one after the other...

Страница 23: ...11 00 V or 21 5 mA then appears in the display Menu Selection Example 5 000 Select digit Set digit Select digit Set digit Menu Selection Example 9 000 Select digit Set digit Lower limit Upper limit pr...

Страница 24: ...Than set the display value for the start of the slope Example 250 0 Select digit Set digit 5 3 3 Define the second scaling point Set input value Menu Selection Example 2 000 Example 300 0 Set display...

Страница 25: ...manually using the red key If the totalizer value exceeds the range 99999 the display blinks once per second Note In the event of a power failure the totalizer value is saved press the key to accept T...

Страница 26: ...100 Min 0 00001 0 0001 x 0 001 Factor and scale influence only the totalizer Setting the factor Menu Selection Select digit Set digit Conversion into other measuring units can be carried out with the...

Страница 27: ...election press the key to accept the selection Page 21 5 5 1 4 Alarm 1 Hysteresis Here hysteresis means The difference in thresholds between switching on and switching off This difference should be se...

Страница 28: ...cal reset Alarm output can either be reset manually via the red key or via a reset pulse on the MP input If is selected as the function and is displayed then the alarm output can only be reset manuall...

Страница 29: ...ected as the function and is displayed then the alarm output can only be reset manually and or electrically if the to talizer reset parameter is programmed as Note The Display Hold function is off pre...

Страница 30: ...erference from mains line and the environment mains hum the instru ment must be set to the local mains frequency Menu Selection Local power line 60 Hz Local power line 50 Hz press the key to accept th...

Страница 31: ...e not measured The input value is higher than 11 0 V or above 21 5 mA Page 29 Current measured value MIN value when activated MAX value when activated Alarm 1 when activated Alarm 2 when activated Tot...

Страница 32: ...ut has been programmed for the Reset function Depending on the setting the resetting is carried out either manually with the red key and or electrically with a high pulse 4V 5 ms at the reset input Re...

Страница 33: ...rties des valeurs limite 5 5 1 Valeur limite 1 Sortie de valeur limite1 20 5 5 1 1 Activation d sactivation de la valeur limite 1 20 5 5 1 2 Affectation de la valeur limite 1 20 5 5 1 3 S lection du m...

Страница 34: ...tant des risques d explosion ni dans les domaines d utilisation exclus par la norme EN 61010 Partie 1 7 L afficheur digital ne doit tre utilis que s il a t encastr dans les r gles de l art conform men...

Страница 35: ...15 50 mA Ex cutions CC Sortie de tension 10 V CC 2 30 mA uniquement Les alimentations d nergie auxiliaires sont isol es galvaniquement des entr es des sor ties de valeur limite et de la tension d ali...

Страница 36: ...X1 X2 X2 Page 9 1 2 3 4 5 6 7 8 9 10 11 1 1 1 9 GND3 pour Uout 10 Uout 10 V 30 mA 11 Uout 24 V 50 mA seulement pour alimentation 90 260 V AC 8 Entr e IMP Reset Latch val limite Display Hold RAZ totali...

Страница 37: ...uer un choix soit r gler une valeur Appuyer sur la touche L affichage cesse d alterner Effectuer un choix Avec la touche faire d filer toutes les possibilit s l une apr s l autre Confirmer un choix Ap...

Страница 38: ...e D passement par le haut si le signal de mesure d passe 11 00 V ou 21 5 mA le message suivant s affiche Menu Choix Exemple 5 000 Choisir la d cade R gler le chiffre Choisir la d cade R gler le chiffr...

Страница 39: ...valeur d affichage pour le d but de la courbe de fonctionnement Exemple 250 0 Choisir la d cade R gler le chiffre 5 3 3 D finition du deuxi me point caract ristique R gler la valeur d entr e Menu Choi...

Страница 40: ...lcul e par le totalisateur en d finissant la position du point d cimal selon les besoins N B Pour optimiser la pr cision il est conseill d utiliser toute la plage d afficha ge pour repr senter la vale...

Страница 41: ...ge du multiplicateur Menu Choix Choisir la d cimale R gler le chiffre Le multiplicateur permet de convertir le r sultat en d autres unit s de mesure Confirmer avec Confirmer avec Page 19 R glage de l...

Страница 42: ...t possible d affecter la valeur limite soit au totalisateur soit la valeur instan tan e Confirmer avec Confirmer avec Confirmer avec Page 21 5 5 1 4 Hyst r sis pour la valeur limite 1 Hyst r sis signi...

Страница 43: ...tion manuelle et lectrique La sortie de valeur limite peut tre r initialis e manuellement l aide de la touche rouge ou lectriquement par une impulsion de r initialisation sur l en tr e MPI Si la fonct...

Страница 44: ...nt par une impulsion de r initialisation sur l en tr e MPI Si la fonction s lectionn e affich e est la sortie de va leur limite ne peut tre r initialis e manuellement et ou lectriquement que si le par...

Страница 45: ...leur MIN et comme valeur MAX 5 7 Filtre antironflement Pour r duire les parasites provenant du r seau ou de l environnement ronflement il faut r gler l appareil sur la tension du r seau local Menu Cho...

Страница 46: ...nal de mesure est sup rieur 11 0 V ou 21 5 mA Page 29 Valeur mesur e courante Valeur minimale si activ e Valeur maximale si activ e Valeur limite 1 si activ e Valeur limite 2 si activ e Total 6 1 Modi...

Страница 47: ...ue si la fonction RAZ a t param tr e pour l en tr e MPI Selon le r glage la remise z ro se fait manuellement en appuyant sur la touche rouge et ou lectriquement par une impulsion haute 4 V 5 ms sur l...

Страница 48: ...totalizador 19 5 5 Valores l mite Salidas de valores l mite 5 5 1 Valor l mite 1 Salida de valores l mite 20 5 5 1 1 Activar o desactivar el valor l mite 1 20 5 5 1 2 Asignar el valor l mite 1 20 5 5...

Страница 49: ...para zonas con riesgo de explosiones y zonas de aplicaci n excluidas en EN 61010 Parte 1 7 El indicador digital debe utilizarse en las debidas condiciones de montaje relati vas al cap tulo Datos t cn...

Страница 50: ...V 15 50 mA En versiones DC s lo salida de tensi n DC 10V 2 30 mA Los suministros de energ a auxiliar est n separados por aislamiento galv nico de las ent radas las salidas de valores l mite y la tensi...

Страница 51: ...Entrada de tensi n X2 X1 X2 X2 P gina 9 1 2 3 4 5 6 7 8 9 10 11 1 1 1 9 GND3 para Uout 10 Uout 10 V 30 mA 11 Uout 24 V 50 mA s lo en alimentaci n de 90 260 V AC 8 Entrada MP Reset Latch Valor l mite...

Страница 52: ...selecci n Acceso a la opci n de men Puede realizar una selecci n o ajustar un valor Pulsar la tecla Se detiene el cambio en el indicador Realizar una selecci n Pulsando la tecla se indicar n todas las...

Страница 53: ...ualizar al ternativamente con el valor de medici n actual Overflow Si la se al de medici n es mayor que 11 00 V 21 5 mA se visualizar en el indicador mediante Men Selecci n Ej 5 000 Seleccionar el d g...

Страница 54: ...nuaci n se ajustar el valor del in dicador para el comienzo de la curva Ejemplo 250 0 Seleccionar el d gito Ajustar la cifra 5 3 3 Definir el segundo punto b sico Ajustar el valor de entrada Men Selec...

Страница 55: ...izador se formar del resultado obtenido en el totali zador mientras que la coma decimal se colocar en el indicador seg n resulte ne cesaria Observaci n para optimizar la exactitud se recomienda utiliz...

Страница 56: ...en Selecci n Seleccionar el d gito decimal Ajustar el valor Con el factor multiplicador pueden reali zarse conversiones en otras unidades de medici n Guardar con Guardar con P gina 19 Ajustar el despl...

Страница 57: ...de medici n actual Guardar con Guardar con Guardar con P gina 21 5 5 1 4 Hist resis para el valor l mite 1 La hist resis aqu tiene un significado di ferencia de los niveles de respuesta en la activaci...

Страница 58: ...play Hold est desactivada Reset tanto manual como el ctrico La salida de valor l mite puede restablecerse manualmente mediante la tecla roja o el ctricamente mediante un impulso Reset en la entrada MP...

Страница 59: ...nualmente mediante la tecla roja o el ctricamente mediante un impulso Reset en la entrada MP Cuando la funci n seleccionada visualizada es la salida de valor l mite s lo puede ser restablecida manualm...

Страница 60: ...s en la red Para disminuir las interferencias de red y de entorno el aparato debe estar ajustado a la frecuencia de red local Men Selecci n Red local con 60 Hz Red local con 50 Hz Guardar con Guardar...

Страница 61: ...e medir n La se al de medici n es mayor que 11 0V mayor que 21 5 mA P gina 29 Valor de medici n actual Valor MIN si est activado Valor MAX si est activado Valor l mite 1 si est activada Valor l mite 2...

Страница 62: ...l reinicio s lo es posible si la entrada MP fue parametrada para la funci n de reini cio Seg n el ajuste se procede al reinicio ma nual con la tecla roja y o el ctrico con un impulso High 4 V 5 ms en...

Страница 63: ...ungen vorbehalten Subject to change without prior notice Sous r serve de modifications Phoenix Contact GmbH Co KG Flachsmarktstra e 832825 Blomberg Telefon 0 52 35 3 00 Telefax 0 52 35 34 12 0 www pho...

Отзывы: