Software for configuring the Inline controller
107144_en_01
PHOENIX CONTACT
53 / 74
3.5.3
Remote control of the Inline terminals
To access the Inline terminals, the SysMikScaloNetwork establishes a TCP connection to
an I/O server. You can specify the IP address and port of the I/O server via the “Address”
property. The default IP address is the local IP address 127.0.0.1:2015, through which the
local I/O server is contacted. It is also possible to establish the connection to an I/O server
on another device by parameterizing the corresponding IP address.
Figure 3-17
Parameterization of the IP address of the I/O server to be contacted
To prevent unwanted remote control by unknown controllers, you can parameterize a re-
mote control address for the Inline controller in the Niagara Workbench, via “Station, Config,
Drivers, SysMikScaIoNetwork, localPlatform, IoRemoteAddr”. In the delivery state,
255.255.255.255 is entered here – with this setting, remote control is possible from any IP
address. If you enter a special IP address, remote control can only take place from this IP
address. Enter an invalid IP address (empty string) to deactivate remote control. Further-
more, via “Station, Config, Drivers, SysMikScaIoNetwork, localPlatform, IoPort”, you can
specify the TCP port number of the I/O server.
Figure 3-18
Parameterization of the I/O server