ILC 2050 BI
PHOENIX CONTACT
107144_en_01
2.9
Mounting and removing the Inline controller
An Inline station is set up by mounting the individual components side by side. No tools are
required. Mounting the components side by side automatically creates potential and bus
signal connections between the individual station components.
The components are mounted perpendicular to the DIN rail.
Mounting location
Like all other terminals in the Inline product range, the Inline controller has IP20 protection
and is designed for use in a closed control cabinet or control box (junction box) with degree
of protection IP54 or higher.
DIN rail
The Inline controller is mounted on a 35 mm standard DIN rail.
End brackets
Mount end brackets on both sides of the Inline station. The end brackets ensure that the In-
line station is correctly mounted. They secure the Inline station on both sides and keep it
from moving from side to side on the DIN rail. Phoenix Contact recommends using
CLIPFIX 35-5 end brackets (Order No. 3022276).
End plate
The mechanical end of an Inline station is the end plate. It has no electrical function. It pro-
tects the station against ESD pulses and the user against dangerous contact voltages. The
end plate is supplied with the Inline controller.
Mounting position
Mount the Inline controller horizontally (as shown in
ture range specified in
Section “Ambient conditions” on page 58
line controller is mounted in this position.
NOTE: Dangerous contact voltage
During any work on the controller, switch off the power supply to the Inline station and
make sure the supply voltage is protected against unauthorized reactivation.
For notes and instructions on mounting and removing Inline terminals, please refer to the
IB IL SYS PRO UM E user manual (for INTERBUS), the IL SYS INST UM E Inline instal-
lation manual, or the Inline system manual for your bus system.
Fix the DIN rail on which the Inline controller is mounted in several places, especially in
the area around the Inline controller controller. This makes it easier to remove the Inline
controller.
NOTE: Risk of damage during mounting and removal if an Inline terminal is left in
position
When mounting or removing the Inline controller, it must be tilted. Tilting the Inline control-
ler when mounting or removing it can damage the locking hooks and jumper contacts of
the adjacent Inline terminal on the right.
•
Before mounting or removing the Inline controller, detach the right-hand connector of
the Inline controller and the adjacent Inline terminal on the right.
The Inline controller must only be mounted or removed within a temperature range from -
25°C to +55°C.