Software for configuring the Inline controller
107144_en_01
PHOENIX CONTACT
43 / 74
3.3.3
Hardware data point test
Often, the hardware startup and the software startup take place separately, both in terms of
time and personnel. Ideally, the electrical installation work (installation and cabling) is com-
pleted with a data point test and corresponding handover certificate. You can use the
startup webserver to perform the data point test. Here, all input and output signals of the
Inline terminals are clearly displayed. If required, you can manually override outputs and ter-
minal parameters, such as measuring ranges, per channel. Thus, a data point test is possi-
ble, even without application software. When logging out of the startup website (manually
or following timeout), all overrides are automatically canceled.
Figure 3-11
Data point test via the startup website