WP 4000
32
PHOENIX CONTACT
108594_en_04
2.
Fit the wires with wire end ferrules and connect the wires to the socket strip.
3.
Plug the socket strip onto pin strip X1.
4.
Secure the socket strip in place with a screw-type locking to prevent it from slipping out.
2.3.2
Grounding
The grounding is performed with a slip-on sleeve (noiseless ground / functional earth
ground).
1.
Strip approx. 5 mm (0.197") off the wires.
2.
Fit the stripped wires with a slip-on sleeve.
3.
Plug the slip-on sleeve on the flat tab.
Figure 2-21
Noiseless ground
NOTICE: Damage
A separate copper conductor must always be provided for the grounding. The conductor
must have a minimum cross-section of 1.5 mm² (16 AWG) and must be kept as short as
possible.