Swimming pool heat pump
- 47 -
R05
——Stop differential of cooling
This represents the difference between R01 and stop cooling point.
R06
——Start differential of heating
This represents the difference between R02 and start heating point.
R07
——Stop differential of heating
This represents the difference between R02 and stop heating point.
R08
——Min. set point in Cooling
Establishes the minimum limit for setting the Cooling set point
R09
——Max. Cooling set point
Establishes the maximum limit for setting the Cooling set point
R10
——Min. Heating set point
Establishes the minimum limit for setting the Heating set point
R11
——Max. Heating set point
Establishes the maximum limit for setting the Heating set point
Compressor action at cooling mode
R02+R07
R02-R06
R02
R02
Compressor on
Compressor off
Water inlet temperature
Compressor action at heating mode
Compressor action at Automatic mode
R01
R01+R04
R01
R01-R05
Compressor on
Compressor off
Water inlet temperature
R03-R06
R03+R04
R03
Compressor on
Compressor off
Water inlet temperature
Cooling
Heating
Содержание PASRW015
Страница 14: ...Swimming pool heat pump 13 Dimension Model PASRW015 Model PASRW020 030 040...
Страница 15: ...Swimming pool heat pump 14 Model PASRW050S 060S...
Страница 21: ...Swimming pool heat pump 20 13 Hydraulic system Installation sketch map...
Страница 25: ...Swimming pool heat pump 24 Model PASRW040 P Model PASRW050 060S U P...
Страница 29: ...Swimming pool heat pump 28 System diagrams...
Страница 49: ...Swimming pool heat pump 48...
Страница 52: ...Swimming pool heat pump 51 PHNIX Guang Dong PHNIX eco energy solution Ltd...