Swimming pool heat pump
- 46 -
H——System Parameter
H01
——Automatic restart
H01=0: disable automatic restart; H01=1: enable automatic restart
H02
——
Mode
H02=0: only cooling;
H02=1: heating, cooling and automatic;
H02=2: only heating.
H03
——
Temperature unit of measure
H03=0: Centigrade unit; (Other area)
H03=1: Fahrenheit unit.( For North America area)
P——Water pump parameters
P01
——Water pump model
P01=0, water pump will always on except on standby and alarm.
P01=1, water pump will operate depend on compressor, and has 2 minutes delay after the
compressor has stopped;
P01=2, water pump will be started and stopped at regular intervals after compressor stop.
Depend on P02 and P03.
P02
—— Minimum off time before the next pump start.
P03
—— minimum on time that the pump remains on.
P04
——the time of pump advance compressor to start up.
R——Temperature parameter
R01
——Cooling set point
Inlet water setting temp. (Cooling)
R02
——Heating set point
Inlet water setting temp. (Heating)
R03
——AUTO set point (Auto mode)
Target setting temperature for auto mode.
R04
——Start differential of cooling
This represents the difference between R01 and start cooling point.
P04
The action sequence of pump and compressor
Compressor
2min
P03 P02 P03 P02
P03 P02
Pump
P03 P02
P02
Содержание PASRW015
Страница 14: ...Swimming pool heat pump 13 Dimension Model PASRW015 Model PASRW020 030 040...
Страница 15: ...Swimming pool heat pump 14 Model PASRW050S 060S...
Страница 21: ...Swimming pool heat pump 20 13 Hydraulic system Installation sketch map...
Страница 25: ...Swimming pool heat pump 24 Model PASRW040 P Model PASRW050 060S U P...
Страница 29: ...Swimming pool heat pump 28 System diagrams...
Страница 49: ...Swimming pool heat pump 48...
Страница 52: ...Swimming pool heat pump 51 PHNIX Guang Dong PHNIX eco energy solution Ltd...