background image

supply & load cable connections 

 

DBC1210 Installation Manual Rev N.docx   

5

 

 
 

                                          

 

 
 
 
 

                                        

 

      
 
 
 

                                     

 

 
 

                  

 

 

Supply Cables 

The  supply  input  terminals  are  located  toward 
the  centre  of  the  enclosure  and  consist  of 
Earth, Neutral and 3 Phases, which will accept 
up to 16mm

2

 cables.  The supply cables should 

have a capacity of 40A per phase, to allow the 
device to be loaded to its maximum capacity. 
 

Load Cables 

Load  cables  can  be  terminated  on  the  2-way 
Load terminal blocks (two for each channel), a 
Neutral  link  and  an  Earth  link  located  at  the 
centre of the enclosure.  These connectors will 
accept up to 10mm

2

 cables.  

It is important that 

an  individual  output  circuit  is  not  overloaded

.  

Calculate the intended load, and ensure that it 
is below the maximum capacity of an individual 
channel, which is 10A.  To ensure compliance 
with  interference  standards,  the  load  neutral 
cables  must  be  individually  connected  to  the 
neutral link terminals inside the cabinet.  

Never 

use a common neutral at a remote location

 

Load Control Cables 

Load Control cables can be terminated on the 
4  way  and  2  way  terminal  blocks  located 
directly  next  to  the  Load  terminals.  These 
terminals are the outputs for 0 to +10V, DSI or 
DALI  if  selected by  software  setup.    Note  that 
most  types  of  1-10V  HF  fluorescent  ballast 
control  wiring  is  polarity  conscious.  DSI 
ballasts are not polarity conscious. 
 

Emergency Lighting Connections 

Connect  Emergency  Lighting  circuit  active  to 
the  load  side  on  the  circuit  breaker  for  the 
relevant  channel,  as  indicated  by  the  labels 
next  to  the  circuit  breakers.    Do  not  remove 
any  cables  that  may  already  be  terminated  at 
this location. 
 

Energising the Device 

If  it  is  necessary  to  energise  load  circuits 
before  any  control  cables  are  connected,  it  is 
acceptable  to  replace  the  cover  and  energise 
the  device  immediately,  as  the  default  factory 
programming  is  to  have  all  channels  set  to 
100% output.  If there is no output on any or all 
channels,  see  the  troubleshooting  section 
(page 8).  This device should be de-energised 
before terminating the control and data cables.

  

 

 

 

Содержание dynalite DBC1210

Страница 1: ...ler Installation Manual contents Warning 2 Hardware Controls 7 Features 2 Troubleshooting 8 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Supplied by ...

Страница 2: ...s Check Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the spe...

Страница 3: ...fy DBC1210 Dynet Data Cable Terminal Earth Link Data Entry Cable Neutral Link Network Socket Supply or Load Cable Entry Manual Circuit Breakers Service LED service switch 3 phase Supply terminals Load Cable Entry Load Cable Entry Power switch output Dimmer control signal 1 10V DSI or DALI Channel over ride switch Emergency lighting supply ...

Страница 4: ...ttached to the inside of the enclosure The brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DBC1210 can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of the internal component...

Страница 5: ...binet Never use a common neutral at a remote location Load Control Cables Load Control cables can be terminated on the 4 way and 2 way terminal blocks located directly next to the Load terminals These terminals are the outputs for 0 to 10V DSI or DALI if selected by software setup Note that most types of 1 10V HF fluorescent ballast control wiring is polarity conscious DSI ballasts are not polarit...

Страница 6: ... for GND one pair paralleled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair Paralleled for GND Orange White pair Paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The ...

Страница 7: ...ce LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Top Set This control is not used in ballast controllers Accessory Module Socket Accepts a plu...

Страница 8: ...r factor loads and transformer losses Check that the breaker terminals are tight Fluorescent lights won t dim Wrong type of ballast or ballast incorrectly wired Control cable from dimmer to ballasts not installed Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI DALI cable and settings specification Supply 230V 14 50 60Hz 3 Phase Y at 40A per phase Line ...

Отзывы: