background image

troubleshooting 

 

8   

DBC1210 Installation Manual Rev N.docx

 

Check the following list.  If you are still unable to rectify the situation, contact your nearest Dynalite office.  A complete list 
of distributors worldwide can be found on the Internet at:  

www.philips.com/dynalite

 

Please ensure that you have completed the following prior to calling our technical support department. 
 

 

Check all symptoms in the Troubleshooting list 

 

Check for any deviations between the installation and the installation instructions 

 

Make a list of the model numbers of all devices used in the system 

 

 

SYMPTOM 

PROBABLE CAUSE 

ACTION 

Dimmer does not operate at all. No Service LED 
activity. Power supply indicator LED on PCB not 
lit. 

Incorrect  connection  of  mains  supply  or  no 
power available. 

Check  power  supply  to  dimmer.    Check  Line 
and Neutral input connections. 

Power  supply  indicator  LED  lit,  but  no  Service 
LED activity. 

Supply  voltage  too  low,  short  circuit  on 
network.   
Control PCB faulty. 

Check supply  voltage is at least 75% of rated 
voltage.    Check  5V  &  12V  terminal  voltages, 
5V  supply  must  be  present.  Disconnect 
network  bus  and  restore  power.    Replace 
control PCB. 

Dimmer  will  not  respond  to  control  panel  push 
buttons. 

Control 

panel 

incorrectly 

wired.  

Incorrect configuration. 

Check  operation  of  LEDs  on  control  panel.  
Push  button  on  panel  and  study  response  of 
service LED. 

Dimmer  operates  properly  but  circuit  breakers 
keep tripping. 

Instant tripping: - short circuit on load.  
Delayed tripping: - Dimmer overloaded. 

Check load wiring for short circuits. 
Verify  dimmer  loading  with  current  tester 
(don’t  forget  to  de-rate  for  low  power-factor 
loads and transformer losses). Check that the 
breaker terminals are tight. 

Fluorescent lights won’t dim. 

Wrong  type  of  ballast  or  ballast  incorrectly 
wired. Control cable from dimmer to ballasts 
not installed. 

Check  ballast  type.    Check  actual  wiring 
against 

ba

llast  manufacturer’s  diagram. 

Check 1-10V/DSI/DALI cable and settings. 

 
specification 

 

Supply: 

230V ±14% 50/60Hz 3-Phase Y at 40A per phase  

Line Outputs: 

12 x Switched outputs at 10A per channel (total device load 120A) 

Control Outputs: 

12 x  load control outputs, selectable to 1-10V, DSI or DALI Broadcast 

Protection: 

12 x 10A 6kA single pole thermal magnetic circuit breakers 

Switching Device: 

Relay – 50A 230V AC inductive (5000W lighting load rated) 

Control Inputs: 

1 x RS485 DyNet serial port 
1 x programmable dry contact AUX input 

User Controls: 

Service switch 
Diagnostic LED 

Internal Controls: 

Programmable Logic Controller 

DyNet DC VE: 

120mA Supply for approx 6 panels) 

Preset Scenes: 

170 

Supply Terminals: 

Line1, Line2, Line3 
1 x 16mm

2

 max conductor size 

Output Terminals: 

Line for each channel 
1 x 6mm

2

 max conductor size 

Neutral link bar provided 
Earth link bar provided 
0V/DSI/DALI, +V/DSI/DALI for each channel 
1 x 2.5mm

2

 max conductor size 

Cable Entries: 

Mains – 4 x 25mm dia. knockouts mounted on a 85mm x 85mm removable gland plate 
Loads – 6 x 25mm dia. knockouts located on the right hand side of the unit 
Data – 1 x 25mm dia. knockout 

Diagnostic Functions: 

 

Device online/offline status 
Circuit breaker trip monitoring (optional) 
Circuit run time tracking (optional) 

Compliance: 

CE, C-Tick 

Operating Environment: 

Ambient Temperature 40

C max, RH 90% max non condensing 

Construction: 

Alloy/Steel wall mount case with epoxy finish 

Dimensions: 

H 457mm x W 252mm x D 126mm 

Dimensions –RCBO Version: 

H 585mm x W 252mm x D 126mm 

Weight: 

10.25 Kilograms 

 

Содержание dynalite DBC1210

Страница 1: ...ler Installation Manual contents Warning 2 Hardware Controls 7 Features 2 Troubleshooting 8 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Supplied by ...

Страница 2: ...s Check Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the spe...

Страница 3: ...fy DBC1210 Dynet Data Cable Terminal Earth Link Data Entry Cable Neutral Link Network Socket Supply or Load Cable Entry Manual Circuit Breakers Service LED service switch 3 phase Supply terminals Load Cable Entry Load Cable Entry Power switch output Dimmer control signal 1 10V DSI or DALI Channel over ride switch Emergency lighting supply ...

Страница 4: ...ttached to the inside of the enclosure The brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DBC1210 can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of the internal component...

Страница 5: ...binet Never use a common neutral at a remote location Load Control Cables Load Control cables can be terminated on the 4 way and 2 way terminal blocks located directly next to the Load terminals These terminals are the outputs for 0 to 10V DSI or DALI if selected by software setup Note that most types of 1 10V HF fluorescent ballast control wiring is polarity conscious DSI ballasts are not polarit...

Страница 6: ... for GND one pair paralleled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair Paralleled for GND Orange White pair Paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The ...

Страница 7: ...ce LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Top Set This control is not used in ballast controllers Accessory Module Socket Accepts a plu...

Страница 8: ...r factor loads and transformer losses Check that the breaker terminals are tight Fluorescent lights won t dim Wrong type of ballast or ballast incorrectly wired Control cable from dimmer to ballasts not installed Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI DALI cable and settings specification Supply 230V 14 50 60Hz 3 Phase Y at 40A per phase Line ...