15
3-4 Edge and Pulse mode
Manual switch S1 and S2 can set to Edge mode or Pulse mode or Edge-Toggle
mode, default value is Edge mode. But this parameter is useless to PAN09.
3-4-1 Edge mode: this mode is suitable for the bi stable wall switch that has
indicator point on the switch, and the same position correspond to same
state of relay1 and relay2. if the PAN07 relay change the state because
of receiving Z-Wave RF command, it may need two times of change
(switch on to off or switch off to on) to let relay back to the correspond
state.
3-4-2 Pulse mode: this mode is suitable for the toggle type wall switch to swap
the state of Relay1 or Relay2
3-4-3 Edge-Toggle mode: this mode is suitable for the normal bi-stable switch,
every time when change the state of the wall switch will also swap the
state of Relay1 or Relay2
3-5 Threshold of current for Load Caution
This is a warning when the current of load over the preset threshold value, if the
setting value is 600 (6A), when the load current of Relay1 over this value,
PAN07/PAN09 will send current meter report to the node of correspond Group,
the Range of the setting value is from 10 to 600, and the default value is 600
(6A).
3-6 Threshold of KWh for Load Caution
This is a warning when the KWh of load over the preset threshold value, If the
setting value is 10000, when the Accumulated Power Consumption of Relay1 or
Relay2 over this value, PAN07/PAN09 will send KWh Meter Report command to
the node of correspond Group, minimum value is 1KWh and default value is
10000 kWh.
3-7 Relay control mode
3-7-1 Relay controlling is referred to the meter wattage: When PAN07/PAN09
gets an instruction from RF command or the manual switch, to switch on
or off, it will check the wattage of the load first. If the wattage value is
greater than 2 watts, the switch state means ON; on the other hand, it
means OFF. When the switch state is ON, only SWITCH OFF instruction
will be accept; on the other hand, when the switch state is OFF, only
SWITCH ON instruction will be accept.
3-7-2 Control relay directly : Whenever PAN07/PAN09 get an SWITCH ON
instruction, it will close the relay; on the other hand, it will open the relay.
3-8 Restore switch state mode
Whenever the AC power return from lost, PAN07/ PAN09 will restore the relay
switch state which could be All relay stay NC terminal
、
Last relay switch state
、
All relay stay NO terminal. The default setting is Last relay switch state.
3-9 Existence of Endpoint3
:
:
:
:
The endpoint3 of Multi-Channel Command Class is related to relay1 and relay2.
It may be redundant for the need to control relay1 or relay2 individually. When
the Existence of Endpoint3 is set as 0, the endpoint3 of Multi-Channel