3-4 Edge and Pulse mode 

Manual switch S1 and S2 can set to Edge mode or Pulse mode or Edge-Toggle 

mode, default value is Edge mode. But this parameter is useless to PAN09. 

3-4-1 Edge mode: this mode is suitable for the bi stable wall switch that has 

indicator point on the switch, and the same position correspond to same 

state of relay1 and relay2. if the PAN07 relay change the state because 

of receiving Z-Wave RF command, it may need two times of change 

(switch on to off or switch off to on) to let relay back to the correspond 

state.     

3-4-2 Pulse mode: this mode is suitable for the toggle type wall switch to swap 

the state of Relay1 or Relay2 

3-4-3 Edge-Toggle mode: this mode is suitable for the normal bi-stable switch, 

every time when change the state of the wall switch will also swap the 

state of Relay1 or Relay2       

3-5 Threshold of current for Load Caution 

This is a warning when the current of load over the preset threshold value, if the 

setting value is 600 (6A), when the load current of Relay1 over this value, 

PAN07/PAN09 will send current meter report to the node of correspond Group, 

the Range of the setting value is from 10 to 600, and the default value is 600 

(6A).

 

3-6 Threshold of KWh for Load Caution 

This is a warning when the KWh of load over the preset threshold value, If    the 

setting value is 10000, when the Accumulated Power Consumption of Relay1 or 

Relay2 over this value, PAN07/PAN09 will send KWh Meter Report command to 

the node of correspond Group, minimum value is 1KWh and default value is 

10000 kWh. 

3-7 Relay control mode 

3-7-1 Relay controlling is referred to the meter wattage: When PAN07/PAN09 

gets an instruction from RF command or the manual switch, to switch on 

or off, it will check the wattage of the load first. If the wattage value is 

greater than 2 watts, the switch state means ON; on the other hand, it 

means OFF. When the switch state is ON, only SWITCH OFF instruction 

will be accept; on the other hand, when the switch state is OFF, only 

SWITCH ON instruction will be accept.   

3-7-2 Control relay directly : Whenever PAN07/PAN09 get an SWITCH ON 

instruction, it will close the relay; on the other hand, it will open the relay. 

3-8 Restore switch state mode 

Whenever the AC power return from lost, PAN07/ PAN09 will restore the relay 

switch state which could be All relay stay NC terminal

Last relay switch state

All relay stay NO terminal. The default setting is Last relay switch state. 

3-9 Existence of Endpoint3

 

The endpoint3 of Multi-Channel Command Class is related to relay1 and relay2. 

It may be redundant for the need to control relay1 or relay2 individually. When 

the Existence of Endpoint3 is set as 0, the endpoint3 of Multi-Channel 

Содержание PAN07

Страница 1: ...1 PAN07 1C 2C 3C PAN09 1C 2C 3C TWO SPDT Switch module with meter Fig 1 PAN07 Assembling Fig 2 PAN09 Assembling ...

Страница 2: ...ion will be executed as long as the in wall switch does not have Node ID and just connect the switch to main power Note Auto inclusion timeout is 2 minute during which the node information of explorer frame will be emitted once every several seconds Unlike inclusion function as shown in the table below the execution of auto inclusion is free from pressing the On Off button on the Switch The table ...

Страница 3: ...e LED Indication Normal Whatever we switch On and off of the PAN07 PAN09 by S1 S2 or On Off button or RF command the LED will lights up 1 second and then off No node ID Under normal operation when the Switch has not been allocated a node ID the LED flashes on and off alternately at 2 second intervals By pressing S1 S2 or On Off button it will stop flashing temporarily Learning When PAN07 PAN09 is ...

Страница 4: ...Value 0 0x00 Report ON Command Class Switch Binary Switch Binary Report Value 255 0xFF Note If the BASIC_GET SWITCH_GET command follow the switch On Off command it should add 0 5s time delay before the Get command 1 2 BASIC_SET SWITCH_BINARY_SET Since the switch has two relay the load attached to the Switch will turn on or off upon receipt of the following commands from a Z Wave Controller by sett...

Страница 5: ...nd Group The content of Alarm Report Alarm report command Command_Class_Alarm Alarm_Report Alarm Type Command_Class_Alarm Alarm_Report Alarm Type Command_Class_Alarm Alarm_Report Alarm Type Command_Class_Alarm Alarm_Report Alarm Type 0x08 Alarm Level 0xFF 0x08 Alarm Level 0xFF 0x08 Alarm Level 0xFF 0x08 Alarm Level 0xFF 2 2 Response to Meter Get Command The Switch will report its 1 instant Power C...

Страница 6: ... Get Scale 0x04 V Meter Report Command Command Class Meter Meter Report Rate Type 0x01 Meter Type 0x01 Precision 1 Scale 0x04 Size 2 Meter Value V Example Scale 0x04 V Precision 1 Size 2 2 Bytes of V Meter Value 1 0x09 V Meter Value 2 0x01 V AC load Voltage Meter Value 1 256 Meter Value 2 230 5 V 2 2 5 AC load current I When receiving Meter Get Command it will report Meter Report Command to the no...

Страница 7: ...l reply state of Relay1 If endpoint set to 3 and PAN07 PAN09 will reply state of Relay2 Below is an example show a source endpoint 5 send a get command to PAN07 PAN09 endpoint 1 COMMAND_CLASS_MULTI_CHANNEL MULTI_CHANNEL_CMD_ENCAP Source End Point 0x05 this is the endpoint of command owner here we assume endpoint is 5 if the owner doesn t support multi Channel this value will be 0 Bit Address Desti...

Страница 8: ...endpoint of command owner here we assume endpoint is 1 if the owner doesn t support multi Channel this value will be 0 Bit Address Destination End Point 0x02 Bit Address 0 Destination End Point range1 3 Command Class 0x25 Command_Class_Switch_Binary 0x25 Command 0x01 Switch_Binary_Set 0x01 Parameter 1 0x00 ON 0xFF OFF 0x00 2 3 3 METER_SUPPORTED_GET This command is to ask the endpoint of PAN07 PAN0...

Страница 9: ...endpoint of command owner here we assume endpoint is 3 if the owner doesn t support multi Channel this value will be 0 Bit Address Destination End Point 0x01 Bit Address 0 Destination End Point range1 3 Command Class 0x32 Command_Class_Meter_V3 0x32 Command 0x05 Meter_Reset 0x05 2 3 5 METER_GET Using meter get command to get the KWH W V I PF from endpoint of PAN07 PAN09 2 3 5 1 Get KWH from endpoi...

Страница 10: ...wer Consumption 0x000005FD 15 33 KWh Parameter 4 0x00 Parameter 5 0x05 Parameter 6 0xFD 2 3 5 2 Get Instant Power Consumption Watt from endpoint METER_GET example COMMAND_CLASS_MULTI_CHANNEL MULTI_CHANNEL_CMD_ENCAP Source End Point 0x05 this is the endpoint of command owner here we assume endpoint is 5 if the owner doesn t support multi Channel this value will be 0 Bit Address Destination End Poin...

Страница 11: ... Source End Point 0x05 this is the endpoint of command owner here we assume endpoint is 5 if the owner doesn t support multi Channel this value will be 0 Bit Address Destination End Point 0x03 Bit Address 0 Destination End Point range1 3 Command Class 0x32 Command_Class_Meter_V3 0x32 Command 0x01 Meter_Get 0x01 Parameter 1 0x20 Scale V 0x04 PAN07 PAN09 AC load Voltage report example COMMAND_CLASS_...

Страница 12: ...ommand_Class_Meter_V3 0x32 Command 0x01 Meter_Get 0x01 Parameter 1 0x28 Scale A 0x05 PAN07 PAN09 AC load current I example COMMAND_CLASS_MULTI_CHANNEL MULTI_CHANNEL_CMD_ENCAP Source End Point 0x03 Meter report Endpoint3 Bit Address Destination End Point 0x05 Bit Address 0 Destination End Point command owner Endpoint value Command Class 0x32 Command_Class_Meter_V3 0x32 Command 0x02 Meter_Report 0x0...

Страница 13: ...int command owner Endpoint value Command Class 0x32 Command_Class_Meter_V3 0x32 Command 0x02 Meter_Report 0x02 Parameter 1 0xA1 Scale Bit2 1 Rate Type 0x01 Meter Type 0x01 Parameter 2 0x51 Precision 2 Scale Bit1Bit0 0x10 Size 1 Parameter 3 0x63 Power Factor 0x63 0 99 2 Z Wave s Configuration Configuration Parameter Function Size Byte Value Unit Default Description 1 Watt Meter Report Period 2 0x01...

Страница 14: ...r Consumption KW h is 227 55 days 10min 32767 1440 227 55 days 3 3 Selected Relay If Controller not using Multi_Channel command class to access the relay of PAN07 PAN09 you may configure the value of relay to react the Basic Command Class Binary Switch Command Class or Meter Command Class V3 3 3 1 Selecte Relay1 and Relay2 Default select is 3 Set command Relay state Basic_Set or Binary_Switch_Set ...

Страница 15: ... when the KWh of load over the preset threshold value If the setting value is 10000 when the Accumulated Power Consumption of Relay1 or Relay2 over this value PAN07 PAN09 will send KWh Meter Report command to the node of correspond Group minimum value is 1KWh and default value is 10000 kWh 3 7 Relay control mode 3 7 1 Relay controlling is referred to the meter wattage When PAN07 PAN09 gets an inst...

Страница 16: ...WITCH_ALL COMMAND_CLASS_ALARM COMMAND_CLASS_SCENE_ACTIVATION COMMAND_CLASS_SCENE_ACTUATOR_CONF COMMAND_CLASS_PROTECTION COMMAND_CLASS_FIRMWARE_UPDATE_MD_V2 COMMAND_CLASS_MULTI_CHANNEL_V3 COMMAND_CLASS_METER_V3 COMMAND_CLASS_CONFIGURATION Troubleshooting Symptom Cause of Failure Recommendation The Switch not working and LED off 1 The Switch is not connect to the Main power 2 The Switch break down 1...

Страница 17: ...s equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the...

Отзывы: