3.  Z-Wave’s Configuration

Configuration

Parameter

Function

Size

(Byte)

Value

Unit

Default

Description

1

Watt Meter 

Report Period

2

0x00

-

0x7FFF

5s

720

0: Disable Report W   

1~0x7FFF : 

720*5s=3600s=1 hour

2

KWH Meter 

Report Period

2

0x00

-

0x7FFF

10min

6

0: Disable Report KWh

1~0x7FFF : 

6*10min=1 hour

3

Threshold of

current for Load

caution

2

10-1100

0.01A

1100

1100*0.01A = 11A

4

Threshold of

KWh for Load

caution

2

1-10000

1KWh

10000

5

Restore switch 

state mode

1

0-2

1

0 : Switch off

1 : Last switch state

2 : Switch on

6

Manual On/Off

mode

1

0-1

1

0

Disable

manual On/Off

1

Enable

manual On/Off

7

LED indication 

mode

1

1-3

1

1 : Show switch state

2 : Show night mode

3 : One flash mode

8

Auto off timer

2

0-0x7FFF

1s

0

0 : Disable auto off 

function

1-0x7FFF : 1s ~ 

32767s

9

RF off com-

1

0-3

0

0 : Switch off

1 : Ignore

mand mode

2 : Switch toggle

3 : Switch on

11

Manual   Switch

Report mode

1

0-1

1

0 : Disable

1 : Enable

14

Watt differential

report mode

1

0-4

1

0 : Disable

1 : 5%

2 : 10%

3 : 15%

4 : 20%

3-1

 Watt 

Meter Report Period:

    If the setting is  configured for 1hour (set value =720), the  PAN10  will report its

instant power consumption every 1 hour to Group1 node.  The maximum interval

to report its instant power consumption is 45 hours (5s*32767/3600=45hr).  

If the 

      setting value is 0, the auto report function of meter Watt will be disabled.

3-2 KWH Meter Report Period:

      If   the   setting   is   configured   for   1hour   (set   value   =6),   the  PAN10  will   report   its

Accumulated   Power   Consumption   (KWh)   every   1   hour   to   Group1   node.     The

maximum interval to report its Accumulated Power Consumption (KWh) is 227.55

days (10min*32767/1440=227.55 days).

 If the setting value is 0, the auto report 

     function of meter KWh will be disabled. 

3-3 Threshold of current for Load Caution

This is a warning when the current of load over the preset threshold value, if the

setting value is 1100, when the load current of Relay1 over this value, PAN10 will

send current  meter   report to  warn  the  Group1  node,  the Range  of  the setting

value is from 10 to 1100, and the default value is 1100.

3-4 Threshold of KWh for Load Caution

9

Содержание PAN10

Страница 1: ...load current 12A with resistive load of connected lights or appliances When detecting overload state the Switch will be disabled and its On Off button will be lockout of which LED will flash quickly However unplug and re connect the switch will reset its overload condition to normal status Safety Precautions and Installation Avoid installing the unit in storming or raining weather Be sure to isola...

Страница 2: ... not plugged into the electrical outlet properly 2 The Switch break down 1 Check power connections 2 Don t open up the Switch and send it for repair The Switch LED illuminating but cannot 1 Check if the load plugged into the Switch 1 Set the ON OFF switch of the attached load to ON control the ON OFF Switch of the attached load has its own ON OFF switch 2 The switch is protected 2 Unprotected the ...

Страница 3: ...ient temperature for the Module is 0 C 40 C 3 Do not locate the Module where exists combustible substances or any source of heat e g fires radiators boiler etc 4 After putting it into use the body of Module will become a little bit hot of which phenomenon is normal Adding to Z WaveTM Network In the front casing there is an On Off button with LED indicator which is used to toggle switch on and off ...

Страница 4: ...g the instructions provided by the controller manufacturer 2 Pressing On Off button three times within 2 seconds will enter inclusion mode Remove Exclusion 1 Put your Z Wave controller into exclusion mode by following the instructions provided by the controller manufacturer 2 Pressing On Off button three times within 2 seconds will enter exclusion mode 3 Node ID has been excluded 0 5s On 0 5s Off ...

Страница 5: ...Overload When overload state occurs the Switch is disabled of which LED flashes on and off alternately at 0 2 second intervals Overload state can be cleared by unplugging and reconnecting the Switch to the wall outlet Installation 1 Put the in wall switch into a wall box and connect the AC power wire L N to PAN10 connector L N 2 Connect the wall switch to the PAN10 as Fig1 Programming 1 Basic Comm...

Страница 6: ... It supports one association group with one node support for Grouping 1 For group 1 the Switch will report its latest status to Z Wave Controller Grouping 1 includes SWITCH_BINARY_REPORT METER_REPORT ALARM_REPORT 2 1 Auto report to Grouping 1 Maximum Node 1 2 1 1 On Off Event Report When on or off state has been changed it will send Binary Switch Report to the node of Grouping 1 Binary Switch Repo...

Страница 7: ...e W Example Meter Value 1 0x00 W Meter Value 2 0x00 W Meter Value 3 0x03 W Meter Value 4 0xEA W Meter W Meter Value 3 256 Meter Value 4 100 2W 2 2 2 Accumulated Power Consumption KWh When receiving Meter Get Command it will report Meter Report Command to the node Meter Get Command Command Class Meter Meter Get Scale 0x00 KWh Meter Report Command Command Class Meter Meter Report Rate Type 0x01 Mete...

Страница 8: ... Get Command Command Class Meter Meter Get Scale 0x05 I Meter Report Command Command Class Meter Meter Report Rate Type 0x01 Meter Type 0x01 Precision 2 Scale 0x05 Size 2 Meter Value I Example Scale 0x05 I Precision 2 Size 2 2 Bytes of I Meter Value 1 0x01 I Meter Value 2 0x21 I AC load current Meter Value 1 256 Meter Value 2 2 89 A 2 2 6 load power factor PF When receiving Meter Get Command it wi...

Страница 9: ...de 1 0 4 1 0 Disable 1 5 2 10 3 15 4 20 3 1 Watt Meter Report Period If the setting is configured for 1hour set value 720 the PAN10 will report its instant power consumption every 1 hour to Group1 node The maximum interval to report its instant power consumption is 45 hours 5s 32767 3600 45hr If the setting value is 0 the auto report function of meter Watt will be disabled 3 2 KWH Meter Report Per...

Страница 10: ...and mode Whenever a switch off command BASIC_SET BINARY_SWITCH_SET SWITCH_ALL_OFF is received it could be interpreted as 4 variety of commands 3 9 1 Switch Off It switches to OFF state The default setting is Switch Off 3 9 2 Ignore The switch off command will be ignored 3 9 3 Switch Toggle It switches to the inverse of current state 3 9 4 Switch On It switches to ON state 3 10 Manual Switch Report...

Страница 11: ...LASS_PROTECTION COMMAND_CLASS_FIRMWARE_UPDATE_MD_V2 Warning 1 Plug out to disconnect from power supply Do not plug in line 2 Do not exceed the max rating Disposal This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote ...

Страница 12: ...he separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the re ceiver is connected Consult the dealer or an experienced radio TV technician for help This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must acc...

Отзывы: