Installing the RS485-FD Converter 

25048008 

 

Using consistent wiring helps eliminate communication connection errors and makes 
troubleshooting much easier. Use the wire colors shown below when connecting all devices to the 

communication system. 

 

Wire function 

RS485 

PCH (if installed) 

All devices 

1

  alarm signal

*

 

1

  white/green 

1

  white/green 

 

A

  communication  [ Tx –  ] 

A

  blue 

A

  blue 

A

  blue 

B

  communication  [ Tx + ] 

B

  white/blue 

B

  white/blue 

B

  white/blue 

C

  communication  [ Rx –  ] 

C

  orange 

C

  orange 

C

  orange 

D

  communication  [ Rx + ] 

D

  white/orange 

D

  white/orange 

D

  white/orange 

E

  common reference 

E

  green 

E

  green 

E

  green 

Used only in OMNI Select systems with the Phason Communication Hub (PCH). For information about connecting a   

PCH see the installation guide for that specific product. 

 

Common mistakes in communication wiring 

 

Not using the correct type of communication cable

 – the communication cable must be twisted 

pair cable, category 5 (CAT5). You can use either unshielded twisted pair (UTP) or shielded 

twisted pair (STP) cable. Phason does not recommend other types of wire. 
There are additional guidelines to follow when using STP cable. For more information, read 

Using shielded twisted pair (STP) cable

 on page 4. 

 

Running the communication cable in the same conduit as, or beside AC power cables

 – 

routing communication cable in the same conduit as, or beside AC power cables, can cause 
electrical interference and communication failures. Follow the guidelines below when routing 

communication cable. 

 

Do not run the cable in the same conduit as AC power cables. 

 

Do not run the cable beside AC power cables or near electrical equipment. 

 

When crossing other cables or power lines, cross them at a 90-degree angle. 

 

Not continuing the communication wiring properly

 – all the devices on the communication 

channel must be connected in series (in a daisy chain) and the wire must be continued properly 

from one device to the next. When continuing the communication wiring from one device to the 
next, the wires must be connected as shown in the following diagram. 

 

 

 

Содержание RS485-FD

Страница 1: ...the Phason software on your computer to communicate with the devices along a communication channel A communication channel is a continuous line of cable connecting all devices in the series in other...

Страница 2: ...computer 3 Installing the software drivers on the computer Communication cable requirements The following types of cable are acceptable Phason does not recommend other types of wire Unshielded twiste...

Страница 3: ...gory 5 CAT5 You can use either unshielded twisted pair UTP or shielded twisted pair STP cable Phason does not recommend other types of wire There are additional guidelines to follow when using STP cab...

Страница 4: ...other models must be removed using wire cutters For more information about the location of termination resistors see the installation guide for your specific product If you remove the termination resi...

Страница 5: ...f wire to connect to a reference point on the circuit board in place of the E terminal For information about which terminal to use in place of the E terminal see the user manual for the specific devic...

Страница 6: ...m the USB stick 5 When installation has finished connect the RS485 FD to one of your computer s USB ports To manually start driver installation open My Computer or Windows Explorer Browse the USB stic...

Страница 7: ...from temporary high voltage conditions caused by electrical interference power surges and lightning strikes Transient voltages also known as surges or spikes can travel through low voltage data signa...

Страница 8: ...Phone 204 233 1400 Fax 204 233 3252 Phason Inc 2 Terracon Place Winnipeg Manitoba Canada R2J 4G7 E mail support phason ca Web site www phason ca...

Отзывы: