2.4 Field Wiring Terminals
The Phase Connect will accept an incoming voltage range of 100 VAC
– 480 VAC.
Connect incoming power cables to L1 and L2, shown in
, and tighten to 10.5 lb-in,
as shown in
CAUTION:
Installations must comply with NEC and local electrical code requirements.
Failure to do s
o can lead to hazardous situations and may void manufacturer’s warranty.
Table 1
– Input Power Terminal Specifications
Rating
Wire Size
Torque
Input Power (L1, L2)
480 V, 3 A
18
– 6 AWG
10.5 lb-in.
Figure 4
–
Input Power Terminal Locations
2.5 Cable and Wire Routing
All cables should enter the bottom of the enclosure through the conduit openings provided.
Do not route power cables and control wires in the same conduit. If control cables must
intersect power cables, they should cross at right angles to minimize electromagnetic
interference (EMI). See enclosure drawing on page 2 for conduit sizes and locations.
Input Power
Terminals (L1, L2)
and Ground Terminal