20
◎
Suggested wire selection for input/out wirings, e.g. RCP-1600
Figure
System assembly diagram
4-1 RHP
Module A
Module B
Module C
Module D
Module E
STATUS
STATUS
STATUS
STATUS
STATUS
Input/ Output
115VAC
230VAC
+12VDC
+24VDC
+48VDC
Other commonly used wires
Module
1 unit
1 unit
1 unit
1 unit
1 unit
2 unit
2 unit
2 unit
3 unit
4 unit
5 unit
3 unit
4 unit
5 unit
3 unit
4 unit
5 unit
Current
15Arms
9Arms
125Adc
67Adc
33.5Adc
250Adc
134Adc
67Adc
375Adc
500Adc
625Adc
201Adc
268Adc
335Adc
100.5Adc
134Adc
167.5Adc
Minimum Cross-section of copper wire
14AWG UL1015
18AWG UL1015
30mm
22mm
5.5mm
80mm
30mm
22mm
30mm
30mm
50mm
150mm
250mm
325mm
60mm
100mm
150mm
16AWG UL1015
12AWG UL1015
10AWG UL1015
30mm
50mm
60mm
80mm
100mm
125mm
150mm
200mm
325mm
250mm
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Maximum Current
12A
6A
139A
115A
49A
257A
139A
115A
395A
556A
665A
217A
298A
395A
139A
139A
190A
8A
22A
35A
139A
190A
217A
257A
298A
344A
395A
469A
665A
556A
Table 4-1
Suggested wire selection for input/output wirings
Adjustable voltage range
Model
12V
9 ~ 15V
24V
18 ~ 30V
48V
36 ~ 60V
Tabel 3-13
2.
When using PMBus to adjust output voltage, VOUT_COMMAND only can be used to display the rated voltage of the unit and
cannot be
It is VOUT_TRIM that provide voltage trimming function. Taking RCB-1600-12 as an example, to get a 9V
written
.
s
output, please
value of VOUT_TRIM to -3V. Adjustable voltage range for each model is shown as below.
set
4.
Notes on Operation
4.1
Installation Method
◎
Mount the RHP-1U in a 19 inch rack cabinet before operating.
Insert 1
5 pieces of RCP RCB 1600 with the same output voltage and current into the RHP 1U refer to Figure4 1
~
/
-
(
)
-
(
- )
◎
This is a unit with forced air cooling, please keep fans and ventilation holes free from any obstructions. It is suggested that there
◎
should be no barriers within 10cm of the ventilation holes.
Connect AC source to the AC inlets (A, B, C, D, E
) respectively.
◎
3.The value of CURVE_VFLOAT should be set less or equal to CURVE_VBST,If CURVE_VFLOAT is greater than CURVE_VBST, it
will be saved as CURVE_VFLOAT = CURVE_VBST in EEPROM.
3.21 CANBus
Communication Interface
◎
For further CANBus information, Please contact MEAN WELL for detail.
◎
Please refer to our specifications about PV/PC or SVR function.
22