8
VersiStart II 3 ... 15L ..
8.
Connection Power
section (see also connection diagram))
9.
Connection control section
Caution: Danger to life through electric shock!
The motor is
not
physically separated from the mains.
If only soft starts are required, VersiStart II may also be controlled via the main contactor. For this
purpose, the terminals X5 and X6 have to be bridged.
Terminal 1L1:
Terminal 3L2:
Terminal 5L3:
Terminal 2T1:
Terminal 4T2:
Terminal 6T3:
Mains voltage L1
Mains voltage L2
Mains voltage L3
Motor terminal U
Motor terminal V
Motor terminal W
If the contact on the terminals X5 a. X6 is
closed, the motor accelerates with the adjusted
acceleration time ramp. When the contact is
open, the motor decelerates with the adjusted
deceleration time ramp. Please find an approp-
riate time sequence chart in chapter 15.4 on
page 18.
If the contact on the terminals X4 and X5 is
briefly closed, the motor starts with the adjusted
ramp-up time. If the contact X4 and X6 is briefly
opened, the motor runs down with the adjusted
ramp-down time. Please find an appropriate
time sequence chart in chapter 15.4 on
page 18.
Start/
Stop
5
6
1
2
6
4
5
Stop
Start
R1
1
2
R1
Содержание VersiStart II 11L Series