5.3.7 Indoor / Outdoor Units Communication
Protection
If the indoor units do not receive the feedback
signal from the outdoor units for 2 consecutive
minutes, the unit stops. The unit displays the
failure code.
5.3.8 High Condenser Coil Temp. Protection
T3
Resume
Off
Decrease
Hold
5.3.9 Outdoor Unit Anti-Freezing Protection
When T2<4
℃
for 250seconds or T2<0
℃
, the
indoor unit capacity demand is zero and resumes
normal operation when T2>8
℃
and the protection
time is no less than 3 minutes.
5.3.10 Oil Return
Rules for Operation
1. If the compressor frequency continues to be
lower than the frequency set for setting time, the
unit raises the frequency to the frequency set for
setting time and then resumes with the former
frequency.
2. The EXV continues at 300p while indoor units
maintain their operation.
If the outdoor ambient temperature is higher than
the set frequency during oil return, the unit stops
the oil return process.
5.3.11
Low Outdoor Ambient Temperature
Protection
When the compressor is off and T4 is lower than -
35
℃
for 10 seconds, the unit stops and displays
“LP” or “PC0L”
When the compressor is on and T4 remains lower
than -40
℃
for 10 seconds, the unit stops and
displays
“LP” or “PC0L”
When T4 is no lower than -32
℃
for 10 seconds,
the unit exits protection.
5.4 Control and Functions
5.4.1 Capacity Request Calculation
For Old Console series, Old Duct/Cassette/Floor
Ceiling, Old Vertu/Luna Series:
Total capacity Request=
Σ(Norm code × HP) /10×
modify rate+ correction
For All new models(New Wall mounted(Hi-Wall)
series, New Duct/Cassette/Console/Floor Ceiling):
Total capacity Request=
Σ(Norm code × HP) /40×
modify rate+ correction
∑
Cooling Mode:
T1 Ts
3
1
1
e
c
a
4
2
0
2
3
0
1
f
d
b
Capacity area
a
b
c
d
e
f
Norm code (N)
3
2 1.5 1 0.5 0
Model
9K
12K
18K
24K
HP
1.0
1.2
1.5
2.5
Note: The final result is an integer.
Use the following table and final capacity
request to confirm the operating frequency.
Содержание 3PAMS18-HH-MZO2
Страница 5: ...4 ...
Страница 28: ...27 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor M2OF 18HFN1 M M2OH 18HFN1 M 3PAMS18 HH MZO2 ...
Страница 29: ...28 3PAMSH18 MZO2 5 ...
Страница 30: ...29 6 2 Wiring diagram of 1 drive 3 outdoor M3OF 27HFN1 M ...
Страница 31: ...30 3PAMSH27 MZO3 3PAMS27 HH MZO3 ...
Страница 32: ...31 M3OH 27HFN1 M ...
Страница 33: ...32 6 3 Wiring diagram of 1 drive 4 outdoor M4OF 36HFN1 M ...
Страница 34: ...33 M4OH 36HFN1 M 3PAMSH36 MZO4 ...
Страница 36: ...35 6 4 Wiring diagram of 1 drive 5 outdoor M5OF 48HFN1 M ...
Страница 46: ...45 7 CN53 CN53 Connect to main PCB CN5 8 CN52 CN52 Connect to PFC inductor 9 CN55 CN55 Connect to main PCB CN7 ...
Страница 47: ...46 PCB board of M5OF 48HFN1 M M4OH 36HFN1 M ...
Страница 51: ...50 PCB Board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Страница 53: ...52 IPM board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Страница 72: ...71 Operating els Standby Pic 2 IPM for 2 zone 3 zone ...
Страница 73: ...72 PIC3 Main board LED when power on and unit standby Pic 2 IPM for 4 zone 5 zone Power Standby Operating els ...
Страница 91: ...90 Operating els Standby Pic 2 IPM board for 2 zone 3 zone ...
Страница 92: ...91 PIC3 Main board LED when power on and unit standby Pic 2 IPM for 4 zone 5 zone Power Standby Operating els ...
Страница 93: ...92 PIC 4 Check point button press 1 time for check how many indoor units are connected ...
Страница 99: ...98 IPM board for 4 zone ...
Страница 103: ...102 Two ports of the inductance Inductance ...
Страница 106: ...105 Vs Vcc Vsp FG ...
Страница 110: ...109 ...
Страница 113: ...112 ...
Страница 116: ...115 ...
Страница 120: ...119 Faulty outdoor PCB Trouble shooting ...
Страница 129: ...128 ...
Страница 136: ...135 Red Blue Red Yellow Brown Orange ...
Страница 137: ...136 Brown White ...