Current protection of compressor
Judge 1: Check whether the input
current of the power supply wire
is more than 15A(18K) (For
27K&hyper heat 18K, it is
18.5A.For 36K&hyper heat 27K, it
is 22.5A.For 48K&hyper heat
36K, it is 28A)
Yes
Replace the electric control box
Check whether the
refrigerant system
is ok
Judge 2: Check whether the
outdoor ambient temperature
is higher than 50
No
Stop the unit
Yes
Judge 3: Check whether the
outdoor unit is bad ventilation
No
Make the outdoor unit ventilate well
Yes
Judge 5: The refrigerant pipe is
blocked
No
Let the refrigerant out, then use the high pressure
nitrogen or refrigerant to blow pipe, vacuumize
and charge the refrigerant again
Yes
Judge 4: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Yes
Yes
Replace outdoor main
board,and check whether the
system can run normally
No
Yes
Trouble is solved
Replace outdoor main board
No
Содержание 3PAMS18-HH-MZO2
Страница 5: ...4 ...
Страница 28: ...27 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor M2OF 18HFN1 M M2OH 18HFN1 M 3PAMS18 HH MZO2 ...
Страница 29: ...28 3PAMSH18 MZO2 5 ...
Страница 30: ...29 6 2 Wiring diagram of 1 drive 3 outdoor M3OF 27HFN1 M ...
Страница 31: ...30 3PAMSH27 MZO3 3PAMS27 HH MZO3 ...
Страница 32: ...31 M3OH 27HFN1 M ...
Страница 33: ...32 6 3 Wiring diagram of 1 drive 4 outdoor M4OF 36HFN1 M ...
Страница 34: ...33 M4OH 36HFN1 M 3PAMSH36 MZO4 ...
Страница 36: ...35 6 4 Wiring diagram of 1 drive 5 outdoor M5OF 48HFN1 M ...
Страница 46: ...45 7 CN53 CN53 Connect to main PCB CN5 8 CN52 CN52 Connect to PFC inductor 9 CN55 CN55 Connect to main PCB CN7 ...
Страница 47: ...46 PCB board of M5OF 48HFN1 M M4OH 36HFN1 M ...
Страница 51: ...50 PCB Board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Страница 53: ...52 IPM board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Страница 72: ...71 Operating els Standby Pic 2 IPM for 2 zone 3 zone ...
Страница 73: ...72 PIC3 Main board LED when power on and unit standby Pic 2 IPM for 4 zone 5 zone Power Standby Operating els ...
Страница 91: ...90 Operating els Standby Pic 2 IPM board for 2 zone 3 zone ...
Страница 92: ...91 PIC3 Main board LED when power on and unit standby Pic 2 IPM for 4 zone 5 zone Power Standby Operating els ...
Страница 93: ...92 PIC 4 Check point button press 1 time for check how many indoor units are connected ...
Страница 99: ...98 IPM board for 4 zone ...
Страница 103: ...102 Two ports of the inductance Inductance ...
Страница 106: ...105 Vs Vcc Vsp FG ...
Страница 110: ...109 ...
Страница 113: ...112 ...
Страница 116: ...115 ...
Страница 120: ...119 Faulty outdoor PCB Trouble shooting ...
Страница 129: ...128 ...
Страница 136: ...135 Red Blue Red Yellow Brown Orange ...
Страница 137: ...136 Brown White ...