18
from the vacuum pump to the valve at the bottom
of the cylinder. If the refrigerant is R410A, make
the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and
press the check valve on the charge set to purge
the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4). Open the valves (Low side) on the charge set
and charge the system with liquid refrigerant
If the system cannot be charge with the specified
amount of refrigerant, or can be charged with a
little at a time (approximately 150g each time) ,
operating the air conditioner in the cooling cycle;
however, one time is not sufficient, wait
approximately 1 minute and then repeat the
procedure.
5).When the electronic scale displays the proper
weight, disconnect the charge hose from the 3-
way valve’s service port immediately
If the system has been charged with liquid
refrigerant while operating the air conditioner, turn
off the air conditioner before disconnecting the
hose.
6). Mounted the valve stem caps and the service
port. Use torque wrench to tighten the service
port cap to a torque of 18N·m (13.27 ft·lbs).
Always leak check after servicing the refrigerant
system.
For M3OF-27HFN1-M/M4OF-36HFN1-M/M5OF-
48HFN1-M/M2OH-18HFN1-M/M3OH-27HFN1-M/
M4OH-36HFN1-M/
3PAMS48-HH-MZO5
There are one low-pressure centralized valve and
one high-pressure centralized valve, it will be
more time saving when vacuum and recycle
refrigerant. But refer to the previous instruction
when vacuum and recycle refrigerant.
Содержание 3PAMS18-HH-MZO2
Страница 5: ...4 ...
Страница 28: ...27 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor M2OF 18HFN1 M M2OH 18HFN1 M 3PAMS18 HH MZO2 ...
Страница 29: ...28 3PAMSH18 MZO2 5 ...
Страница 30: ...29 6 2 Wiring diagram of 1 drive 3 outdoor M3OF 27HFN1 M ...
Страница 31: ...30 3PAMSH27 MZO3 3PAMS27 HH MZO3 ...
Страница 32: ...31 M3OH 27HFN1 M ...
Страница 33: ...32 6 3 Wiring diagram of 1 drive 4 outdoor M4OF 36HFN1 M ...
Страница 34: ...33 M4OH 36HFN1 M 3PAMSH36 MZO4 ...
Страница 36: ...35 6 4 Wiring diagram of 1 drive 5 outdoor M5OF 48HFN1 M ...
Страница 46: ...45 7 CN53 CN53 Connect to main PCB CN5 8 CN52 CN52 Connect to PFC inductor 9 CN55 CN55 Connect to main PCB CN7 ...
Страница 47: ...46 PCB board of M5OF 48HFN1 M M4OH 36HFN1 M ...
Страница 51: ...50 PCB Board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Страница 53: ...52 IPM board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Страница 72: ...71 Operating els Standby Pic 2 IPM for 2 zone 3 zone ...
Страница 73: ...72 PIC3 Main board LED when power on and unit standby Pic 2 IPM for 4 zone 5 zone Power Standby Operating els ...
Страница 91: ...90 Operating els Standby Pic 2 IPM board for 2 zone 3 zone ...
Страница 92: ...91 PIC3 Main board LED when power on and unit standby Pic 2 IPM for 4 zone 5 zone Power Standby Operating els ...
Страница 93: ...92 PIC 4 Check point button press 1 time for check how many indoor units are connected ...
Страница 99: ...98 IPM board for 4 zone ...
Страница 103: ...102 Two ports of the inductance Inductance ...
Страница 106: ...105 Vs Vcc Vsp FG ...
Страница 110: ...109 ...
Страница 113: ...112 ...
Страница 116: ...115 ...
Страница 120: ...119 Faulty outdoor PCB Trouble shooting ...
Страница 129: ...128 ...
Страница 136: ...135 Red Blue Red Yellow Brown Orange ...
Страница 137: ...136 Brown White ...