background image

 6

 INSTALLATION INSTRUCTIONS

Fig.4

Correct orientation 

of Installation Plate

Wall

Indoor

Outdoor

5-

7m

m

Fig.6

Fig.5

Indoor unit installation (wall-mounted type)

2. Drill a hole in the wall
  

Note:
  

1.  Fit the Installation Plate

1. Fit the installation plate horizontally

    on structural parts of the wall with 

    spaces around the installation plate.

2. If the wall is made of brick, concrete 

    or the like, drill five or eight 0.197 inches ( 5mm) 

    diameter holes in the wall. Insert Clip anchor 

    for appropriate mounting screws.

3. Fit the installation plate on the wall 

    with five or eight  type “A” screws.

Fit the Installation Plate and drill 

holes in the wall according to the 

wall structure and corresponding 

mounting points on the installation 

plate. The Installation Plate may be 

slightly different according to the

different models of indoor unit. 

(

Dimensions are in “inch” unless 

  otherwise stated)

1. Determine hole positions according

    to the diagram detailed in Fig.5. Drill 

    one (1) hole (2.5 inches (65mm)) slanting slightly 

    to outdoor side.

3. Connective Pipe and Drainage 
     Installation

1. Run the drain hose sloping downward. 
    Do not install the drain hose as 
    illustrated in Fig.7.

Drainage

Fig.7

Do not block water flow by a rise.

Do not put the end of 

drain hose into water.

Indoor unit outline

Installation plate

11

.5

in

.

Right rear side 

refrigerant

pipe hole  2.6in.

Left rear side 

refrigerant

pipe hole  2.6

36.14in.

1.

8

7.28in.

5.91in.

A

1.

8

B

Right rear side 

refrigerant

pipe hole  2.6in.

Installation plate

Indoor unit outline

Left rear side 

refrigerant

pipe hole  2.6

6in.(150mm) or more to ceiling

4.8in.(120mm) 

or more to wall

4.8in.(120mm) or 

more to wall

 Model A (A: 28, B: 9.84, C:3.94, D: 4.33)

 Model A (A: 28, B: 9.84, C: 3.94, D: 4.33)

 Model A (A: 36.2, B: 11.5, C:5.9, D: 7.3)

Model B( 

)

A: 31.1, B:10.43, C:3.94, D: 5.9 

Model B( 

)

A: 31.1, B:10.8, C:3.94, D: 3.35 

Model C( 

)

A: 33.5, B:11.4, C:3.94, D: 4.53 

Model B( 

)

A: 39.2, B:11.5, C:5.9, D:7.9 

Model C( 

)

A: 33.5, B:12, C:5.9, D:5.7 

1.

8

C

D

6in.(150mm) or more to ceiling

4.8in.(120mm) or 

more to wall

4.8in.(120mm) 

or more to wall

Right rear side 

refrigerant

pipe hole  2.6in.

Left rear side 

refrigerant

pipe hole  2.6in.

1.

8

1.

8

6in.(150mm) or more to ceiling

4.8in.(120mm) or 

more to wall

4.8in.(120mm) 

or more to wall

1.

8

0

.2

-0

.3

in

.

(

)

Содержание 1PAMSCH12

Страница 1: ...er please read this manual carefully and keep it for future reference along with your receipt ROOM AIR CONDITIONER Before using your air conditioner please read this manual carefully and keep it for f...

Страница 2: ...e that they do not play with the air conditioner Replacement work shall be performed by authorized personnel only Installation work must be performed in accordance with the national wiring standards b...

Страница 3: ...d regulation and these installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it will cause ele...

Страница 4: ...t radiation from the condenser is not restricted Ensure that the clearance around the back of the unit is more than 12 inches 30cm and left side is more than 12 inches 30cm The front of the unit shoul...

Страница 5: ...ize 1 4 6 35mm 3 8 9 53mm 1 2 12 7mm 6 2 Self tapping Screw B ST2 9X10 Remote Control Installation Plate Name of Part Self Tapping Screw A ST3 9X25 Seal for cooling heating models only Drain Joint Tra...

Страница 6: ...ctions should be free from obstructions CAUTION INSTALLATION INSTRUCTIONS 5 CAUTIONS One Two Zone One Three Zone One Four Zone More than 4 73in 12cm r e t l i f r i A Remote control n i 3 7 4 n a h t...

Страница 7: ...ly to outdoor side 3 Connective Pipe and Drainage Installation 1 Run the drain hose sloping downward Do not install the drain hose as illustrated in Fig 7 Drainage Fig 7 Do not block water flow by a r...

Страница 8: ...drain hose with tape securely evenly as shown in Fig 11 Because the condensed water from rear of the indoor unit is gathered in evaporative drain pain box and is piped out of room do not put anything...

Страница 9: ...nit and the wall Remove after finished piping 4 Push the lower part of the indoor unit up on the wall then move the indoor unit from side to side up and down to check if it is hooked securely 4 Indoor...

Страница 10: ...e installation board Drill four holes of 0 5 inches 12mm 2 5 inches 50 55mm deep at the selected positions on the ceiling Then embed the expansible hooks fittings Face the concave side of the installa...

Страница 11: ...r 3 8 inches 10 12mm Refer to Fig 17 2 Install The Panel 1 Remove the inlet grid CAUTIONS a Slide two grid switches toward the middle at the same time and then pull them up Refer to Fig 21 o b Draw th...

Страница 12: ...s outlet has been reduced to about 0 16 0 24 inches 4 6mm The edge of the panel should contact with the ceiling well Refer to Fig 24 Do not over tighten the screw Fig 25 If the gap between the panel...

Страница 13: ...rge Before installing condensate water pipeline determine its route and elevation to avoid intersection with other pipelines and ensure slope is straight Support drain link per code The drainage pipe...

Страница 14: ...e Drain tee Water flow Water flow Water flow Water flow Water flow Water flow Water flow Water flow Drain tee Water flow Water flow Keep a certain degree Branch pipe Branch pipe Gas Gas Main pipe Main...

Страница 15: ...units The drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong operation of water level switch Refer to the following picture for installation reference 4 Liftin...

Страница 16: ...ed suspending installation the installation bracket should accord with technique requirement in the installation bracket diagram The installation wall should be solid brick concrete or the same intens...

Страница 17: ...an the measured distance 4 Cut the cable 59 1 inches 1 5m longer than the pipe length 1 Flaring work Fig 53 B Burr removal 1 Completely remove all burrs from the cut cross section of pipe tube 2 Put t...

Страница 18: ...tage should be in the range of 90 110 of rated voltage 3 The creepage protector and main power switch with a 1 5 times capacity of Max Current of the unit should be installed in power circuit 4 Ensure...

Страница 19: ...ed The power is supplied from the Outdoor Unit The Indoor Units are connected with signal wires or power cords are connected reliably and correctly or the air conditioner could not run normally Fig 62...

Страница 20: ...3 S A L A N A L C N C S C L B N B S B L A N A S A L B L C L D N B N D N C S C S D S B NOTE please refer to the following figures if the client wants to wire by themselves ELECTRICAL WORK 19 Model A Mo...

Страница 21: ...of power source 4 Confirm that electrical capacity is sufficient 5 See to it that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate 6 Confirm tha...

Страница 22: ...the outdoor unit Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage Pipe length and refrigerant amount Connective pipe length Less than 16 41 f...

Страница 23: ...flare nut again Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure 7 Remove the charge hose from the Low pressure charge hose 8 Fully open the pa...

Страница 24: ...e nut connections and electrical safety check Check that all tubing and wiring have been properly connected Check that the gas and liquid side service valves are fully open 1 Connect the power press t...

Отзывы: