INSTALLATION INSTRUCTIONS
3. Drainage pipe installation
(1) Installation principle
(2) Drainage pipe selection
Capacity(x1000Btu)
12
2.4
18
4
24
6
30
7
36
8
42
10
48
12
60
14
Water flowrate(g/h)
Ensure at least 1/100 slope of the drainage
pipe.
Adopt suitable pipe diameter.
Adopt nearby condensate water discharge.
Before installing condensate water pipeline,
determine its route and elevation to avoid
intersection with other pipelines and ensure
slope is straight.
Support drain link per code.
The drainage pipe diameter shall not be smaller than the drain hose of indoor unit.
According to the water flowrate and drainage pipe slope to choose the suitable pipe, the
water flowrate is decided by the capacity of indoor unit.
Fig.28
(4) Water-pump drainage
The maximum lifting height is 29.5 inches.
7.9in.
39.4-59.1in.
29
.5
in
.