12
set in:
MENU Boiler Settings Burner
Settings
.
7.10
HUW settings
The equipment controls the temperature of
HUW container if a HUW temperature sensor
is connected. Using the parameter of
HUW
pump mode
the user can:
switch-off HUW container filling by
setting this parameter at
OFF
,
set HUW priority (
Priority
parameter)
–
boiler pump is OFF and mixer closed to
fill HUW water faster.
set simultaneous (parallel) operation of
HUW and boiler pumps using the
parameter
"No priority"
7.11
Setting
the
preset
HUW
temperature
Preset HUW temperature may be set in:
MENU HUW settings
7.12
Activation of SUMMER function
To activate the SUMMER function, which
allows filling the HUW container in summer
without having to heat up the central heating
system, set the parameter SUMMER mode.
MENU HUW settings
In the SUMMER mode, all heat
recipients may be OFF, therefore,
make sure the boiler will not be
overheated.
If a weather sensor is connected, the
SUMMER function may be automatically
activated using the parameters: AUTO
Summer
mode,
SUMMER
switch-on
temperature and SUMMER switch-off
temperature.
7.13
Disinfection of HUW container
The regulator has a function of automatic,
periodic heating of the HUW container to 70
°C to el
iminate bacterial flora from the HUW
container.
Keep the tenants informed of
activating disinfection function as
there is a risk of being burnt with
hot utility water.
Once a week on Sunday at 2:00 A.M the
regulator
rises
the
HUW
container
temperature to
70 °C.
Do not turn on the
disinfection function while support of HUW is
turned off.
7.14
Mixer circle settings
Settings of the first mixer circle are in the
menu:
MENU
→
Mixer 1,2,3,4,5 settings
Mixer settings (without weather sensor)
It is required to set manually desired
temperature in mixer’s heating c
ircle using
parameter
Preset mixer temperature,
e.g. 50
°C
degrees. Such should be a value to
provide required room temperature.
After connecting a room thermostat, value of
decline in preset mixer temperature from
thermostat should be set (parameters
mixer
room thermostat
e.g. 5
°C
degrees). This
value should be chosen experimentally. A
room thermostat can be a traditional one or
a room panel ecoSTER200. After activating
the thermostat, mixer preset temperature
will be reduced. When this value is reduced
correctly then room temperature increase
will be stopped.
Mixer with weather sensor setting (without
room panel ecoSTER200)
Set the parameter
mixer weather control
in
position on. Adjust a weather curve
according to point 7.15.
Using the parameter
paralel curve movement
set required room temperature according to
a formula:
Required room temperature = 20°C +
heating curve paralel movement.
Example.
To reach room temperature 25°C value of
heating curve movement must be set for
5°C. To reach room temperature 18°C value
of heating curve parallel movement must be
set for -
2°C.
Содержание KSP Duo
Страница 1: ...Operation and maintenance manual for the boilers with feeder KSP Duo...
Страница 22: ......
Страница 23: ......
Страница 26: ......
Страница 31: ...REGULATOR INSTRUCTION MANUAL ecoMAX 910R1...
Страница 41: ...USER MANUAL OF CONTROLLER INSTALLATION AND SERVICE SETTINGS ecoMAX 910R1...
Страница 47: ...23...
Страница 71: ...47...
Страница 73: ...Quatro PSQ SCREW CONVEYOR FEEDER U S E R S MA N UA L Updated user s manual are available at www pereko pl...
Страница 82: ......
Страница 84: ...wer 13 12 2017 r...