TTD-08A Electromechanical Box Tripod Turnstile
15
Standard orientation of RC panel in regard to the housing is shown in Fig. 8. If working
space of the operator is located on the opposite side of the housing, then for convenience
of operation it is necessary to swap RC panel cables, connected to contacts
Unlock A
and
Unlock B
, as well as
Led A
and
Led B
correspondingly (see Table 2).
Note:
The WRC is connected to the contacts
GND
,
Unlock A
,
Stop
and
Unlock B
of the
XS1
connector block. Power supply of the WRC is connected to the contact
+12V
of
the
XS1
connector block.
Table 2 – RC-cable connection to the XS1 connector block
contacts for standard and reverse RC-panel orientation
№
Contact
RC-panel orientation
Standard
Reverse
5
GND
black
black
6
Unlock A
white
green
7
Stop
blue
blue
8
Unlock B
green
white
9
Led A
yellow
red
10
Led Stop
orange
orange
11
Led B
red
yellow
5.3.2
Emergency opening device Fire Alarm
The emergency opening device is connected to the contacts “
Fire Alarm”
and “
GND”
of the
XS1
connector block in accordance with the connection layout (see Fig. 13).
If the “
Fire Alarm
” input is not used, it is necessary to set a jumper between the contacts
“
Fire Alarm
” and “
GND
”. This jumper is preset at the factory.
During release of control signal on
Fire Alarm
input, turnstile switches to the emergency
Fire Alarm
passageway opening.
In this mode all incoming turnstile control signals are
disregarded. Turnstile rotation mechanism is blocked for rotation in both directions. Central
barrier arm falls down automatically by gravity and takes a vertical position which opens
the passageway. The following indication in both directions is displayed simultaneously on
indication modules: alternate switching on of green (for 1.25 sec) and red (for 0.25 sec)
turnstile indicators.
If signal
Fire Alarm
comes on the turnstile during the passage, then on indication blocks
appears an indication of
Fire Alarm
mode, but rotation mechanism blocking and passage
emergency opening will take place only after resetting of barrier arm to its home position.
After release of control signal
Fire Alarm
on indication modules
appears red indicator of
passage denial and turnstile switches to the sleep mode with a dropped barrier. To
proceed with the work, a barrier arm has to be manually set in horizontal position, where it
fixes.
5.3.3
Control of the turnstile in ACS
Turnstile can be used as optional equipment while working as a part of ACS. Turnstile is
provided for installation of built-in access card readers under plastic side covers.
The ACS controller outputs are connected to the contacts
GND
,
Unlock A
,
Stop
and
Unlock B
of the
XS1
connector block.