WCS DG310

Commissioning

 2

0

1

7

-1

2

11

If the interface module is operated as the first or last physical device as a 422, a bus termination 
must also occur. By moving the "Rx 422 Termination" or " Tx 422 Termination

 slide switch to 

"On", the integrated terminators can be activated in the Rx or Tx direction.

DeviceNet Termination

If the interface module is located at the beginning or end of the data cable to the control panel, 
there must be a bus termination at this gateway. To do this, set the "Termination" (DeviceNet) 
sliding switch to "On". This activates the DeviceNet terminator (220

) built into the interface 

module.

More information about bus termination can be found in the general fieldbus literature.

4.3

Operating modes

Configuration mode

The configuration mode is used to configure the WCS-DG310 interfaces. The following settings 
are possible in this mode:

1. Install script

2. Update firmware

3. Configure the interface module

The interface module will start in this mode if the rotary switches S4 and S5 are both in position 
"F." The interface module sends its switch-on message immediately after it has been switched 
on in configuration mode. In configuration mode, the interface module always works with the 
settings 9600 baud, no parity bit, 8 data bits, and 1 stop bit. The RS state LED always flashes 
red, the "Error No/ Select ID" LEDs have no significance for the user. The configuration mode is 
included in all software revisions.

Test mode

Setting test mode

Test mode is set by putting both switches S4 and S5 into position "E." No other switches are 
considered when setting test mode. With these settings, the interface module must be 
restarted (by disconnecting it briefly from the power supply). In test mode, the interface module 
always works with the settings 9600 baud, no parity bit, 8 data bits, and 1 stop bit. Test mode 
can be useful to get the interface module to integrate into the specific environment, e.g., in 
order to test the parameters of the RS 485 interface.

Test mode functionality

After restarting in test mode, the gateway will send the values 0 - 15 in hexadecimal form 
("0"..."F") in ASCII encoding to the serial side, in a 1-second rhythm. At the same time, the 
same values are sent on the DeviceNet side in binary form. The state LED on the RS 485 side 
will flash red in this mode, the "Error No/Select ID" LEDs will display the value currently being 
sent in binary form. In addition, each character received on one of the interfaces is sent back 
out on the same interface as a local echo. On the DeviceNet side, only the first byte is used for 
the local echo, i.e., only the first byte of the bus data is checked both when receiving and 
sending. The bus data does not change with respect to the previous data.

Note!

Rotary switch S4, rotary switch S5, DIP switch

For information on setting rotary switches S4 and S5 as well as the DIP switch, see see chapter 
4.4.

Содержание WCS DG310

Страница 1: ...WCS DG310 WCS DeviceNet Interface Module FACTORY AUTOMATION MANUAL...

Страница 2: ...Terms of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in...

Страница 3: ...on 7 4 Commissioning 9 4 1 Meaning of LEDs 9 4 2 Meaning of Switches 10 4 3 Operating Modes 11 4 4 Connecting the WCS Reader 12 4 5 Connection to the Control Panel 12 4 6 Data Exchange in DeviceNet 13...

Страница 4: ...icable EU type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Target Group Personnel Responsibility...

Страница 5: ...in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indicate...

Страница 6: ...485 interface and from the WCS DG310 to the control panel via the DeviceNet protocol You can connect up to four WCS readers of type LS221 or LS121 If you connect several WCS readers they must have dif...

Страница 7: ...2 to terminal 6 Tx 422 2 Connect terminal 5 Rx 422 to terminal 7 Tx 422 Note Grounding of the mounting rail The mounting rail must be grounded to the switch cabinet The connection wire must have a cro...

Страница 8: ...ating voltage interface module operating voltage WCS reader 2 0 V Pwr Ground interface module ground WCS reader Table 3 2 Terminal X2 Caution Damage to the device Connecting an alternating current can...

Страница 9: ...error and or warning number via the Error No Select ID LEDs BusState LED DeviceNet interface state Lights up green Connected to the DeviceNet master Flashes green No connection to the DeviceNet maste...

Страница 10: ...or 0 1 1 0 6 Reserved 0 1 1 1 7 Communication WCS reader RS send buffer overflow 1 0 0 0 8 Communication WCS reader receive buffer overflow 1 0 0 1 9 Communication WCS reader RS timeout 1 0 1 0 10 Gen...

Страница 11: ...EDs have no significance for the user The configuration mode is included in all software revisions Test mode Setting test mode Test mode is set by putting both switches S4 and S5 into position E No ot...

Страница 12: ...0 You can connect up to 4 WCS readers to an interface module via an RS 485 cable The supplied default address of each WCS reader is 0 Refer to the configuration instructions for the WCS reader if you...

Страница 13: ...DG310 you can only query the data from the master via polling access The sending of a function byte is likewise only possible in polling mode Polling In polling a function byte is sent from the master...

Страница 14: ...s sent every 5 ms In this case the pause time is necessary to avoid overloading the DeviceNet bus Interface module data format for one WCS reader 4 7 EDS configuration file To assist with the configur...

Страница 15: ...in line connection must end with a terminator The RS 485 terminators are integrated in the WCS readers and can be switched on and off with the interface module If only one WCS reader is connected one...

Страница 16: ...WCS reader at the end of the data line For both WCS readers the RS 485 terminator is activated The interface module is located between these two heads and does not have an RS 485 terminator Each WCS...

Страница 17: ...between the interface module and the first WCS reader through a short spur length 1 m Use a bus terminal to connect the spur Figure 5 3 Connection of two reading heads Version B The wiring version use...

Страница 18: ...n Position and Speed operating mode 6 bytes are reserved for each WCS reader Pxx position data P00 LSB Sxx speed in multiples of 0 1 m s S00 LSB Example Byte 5 00011011 27 corresponds to 2 7 m s A1 A0...

Страница 19: ...outside of the code rail not a position value Good P0 P18 0 WCS reader partly outside the code rail P0 1 P2 to P18 0 WCS reader completely outside of the code rail 1 0 0 Current position value binary...

Страница 20: ...oss section and one pair for the RS 485 data line The table shows the possible cable lengths depending on the cable capacitance core core The number of connected WCS readers is of no significance SSI...

Страница 21: ...S WCS DCF Capacitance core core 95 pF m 60 pF m Cross section 0 14 mm2 0 25 mm2 Number of wires 6 3 x 2 6 3 x 2 External diameter 5 8 mm 7 5 mm Temperature range 30 C 70 C 40 C 70 C Order designation...

Страница 22: ...s GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Pac...

Отзывы: