Commissioning
4.2
Meaning of switches
The WCS-DG310 interface module has 6 switches with the following
functions:
Rx 422/Tx 422 Termination (serial interface)
If the interface module is operated as the first or last physical device in an RS485 bus, there
must be a bus termination on this gateway. To do this, set the slide switch "Rx 422 Termination"
to "Off" and the slide switch "Tx 422 Termination" to "On". This activates the RS 485 terminator
(150
Ω
) built into the interface module.
If you connect only one WCS reader to the WCS-DG310, you must always activate the RS 485
terminator.
ErrorNo/Select ID LED
Error number
A description of the fault
LED8
LED4
LED2
LED1
0
0
0
0
0
Reserved
0
0
0
1
1
Hardware error
0
0
1
0
2
EEPROM error
0
0
1
1
3
Internal memory error
0
1
0
0
4
Fieldbus hardware error or incorrect
fieldbus ID
0
1
0
1
5
Script error
0
1
1
0
6
Reserved
0
1
1
1
7
Communication WCS reader, RS
send buffer overflow
1
0
0
0
8
Communication WCS reader, receive
buffer overflow
1
0
0
1
9
Communication WCS reader, RS
timeout
1
0
1
0
10
General fieldbus error
1
0
1
1
11
Parity or frame check error
1
1
0
0
12
Reserved
1
1
0
1
13
Fieldbus configuration error
1
1
1
0
14
Fieldbus data buffer overflow
1
1
1
1
15
Reserved
Table 4.3
Meaning of the error codes (4 LEDs display "Error No/Select ID", if the "State" is illuminated
red and thus indicates an error or a warning)
Switch designation
Function
Rx 422 Termination
Switchable Rx 422 terminator for the serial interface
Tx 422 or RS 485
Termination
Switchable Tx 422 or RS 485 terminator for the serial interface
Termination (DeviceNet)
Switchable terminator for the DeviceNet bus
Rotary switch S4
Set the number of connected WCS readers (see see chapter 4.4)
Rotary switch S5
No function (always remains in position 0)
DIP switches
Set the node ID and baud rate (see see chapter 4.4)
Table 4.4
Meaning of the switches on the WCS DG-310 interface module