Troubleshooting
2
0
2
2
-1
1
19
8
Troubleshooting
8.1
What to Do in the Event of a Fault
In case of a fault, use the following checklist to determine whether a fault with the vibration
monitoring can be remedied.
If none of the information provided in the checklist solves the problem, contact Fuchs
via your sales office with any queries. Have details of the model number and firmware version
of the sensor ready if possible.
Checklist
Error
Cause
Remedy
Incorrect
measured
value
Vibration sensor not
mounted correctly
Check that the sensor is mounted correctly.
Ensure that the sensor thread is tightened with a
tightening torque of 8 Nm.
Vibration sensor mounted
in the wrong position
The vibration behavior can vary depending on
the measuring point/mounting point. Therefore,
mount the sensor as precisely as possible at the
point where the corresponding vibration behav-
ior should be estimated/monitored.
No IO-Link
connection to
vibration
sensor
The C/Q communication
port on the sensor is not
connected to the IO-Link
master.
The data connection
between the PC
(PACTware), IO-Link mas-
ter, and the sensor is not
working.
Make sure the C/Q communication port is con-
nected to the IO-Link master. Restart PACTware
if necessary.
No voltage supply
Check whether there is a reason for the absence
of the voltage supply, e.g., a faulty fuse. Switch
on the voltage supply.
Table 8.1