AS-i 3.0 EtherNet/IP Gateway with integrated Safety Monitor
EtherNet/IP interface
11.1.3
AS-i Master Object
Class code: 100 (0x64)
1 instance for each AS-i circuit
EC-flags (16-bit)
Attribute
ID
Access
rule
Name
DeviceNet
data type
Default
data value
100 (0x64)
get
ec-flags
UINT (16-bit)
101 (0x65)
get/set
hi-flags
USINT
102 (0x66)
get/set
operational mode
BOOL
103 (0x67)
get
LDS
ULINT
104 (0x68)
get/set
LPS
ULINT
105 (0x69)
get
LAS
ULINT
106 (0x6A)
get
LPF
ULINT
107 (0x6B)
get/set
Store_Actual_Configuration
BOOL
108 (0x6C)
get/set
Store_Actual_Parameters
BOOL
109 (0x6D)
get/set
Change_Slave_Adress
UINT
110 (0x6E)
get/set
Lock push-buttons
BOOL
Tab. 11-10.
EC-flags (16-bit)
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
DA NSE OV EF –
–
–
Pok OR APF NA CA AAv AAs S0
Cok
Tab. 11-11.
Pok: Periphery_Ok
S0: LDS.0
AAs: Auto_Address_Assign
AAv: Auto_Address_Available
CA: Configuration_Active
NA: Normal_Operation_Active
APF: APF
OR: Offline_Ready
Cok: Config_Ok
EF: Earth falut
OV: Overvoltage
NSE Noise
DA: Double address